York R-410A Air Conditioner User Manual


 
528195-YTG-B-0810
Johnson Controls Unitary Products 17
115°F 125°F
1875
77 87.4 9.1 32.0 27.6 19.8 - - - 79.5 10.1 25.8 23.8 16.5 - - -
72 80.3 9.1 49.4 41.6 33.8 26.0 - - 73.0 10.0 45.8 38.2 30.6 23.0 - -
67 73.3 9.0 66.9 55.6 47.8 40.0 32.2 - 66.6 9.9 65.4 52.3 44.7 37.1 29.5 -
62 68.9 8.9 68.9 68.9 57.4 49.6 41.7 33.9 63.9 9.9 63.9 63.9 52.7 45.1 37.5 29.9
2250
77 89.0 9.2 39.7 30.7 21.7 - - - 80.3 10.1 35.7 26.9 18.1 - - -
72 81.7 9.1 55.0 46.0 37.0 28.1 - - 73.8 10.0 51.2 42.4 33.7 24.9 - -
67 74.5 9.0 70.3 61.3 52.4 43.4 34.4 - 67.3 9.9 66.7 57.9 49.2 40.4 31.7 -
62 70.1 9.0 70.1 70.1 62.9 53.9 44.9 35.9 64.5 9.9 64.5 64.5 58.1 49.3 40.6 31.8
57 69.6 9.0 69.6 69.6 63.3 54.4 45.4 36.4 63.9 9.9 63.9 63.9 57.6 48.8 40.1 31.3
2625
77 90.5 9.2 47.4 33.7 23.6 - - - 81.1 10.1 45.5 30.1 19.8 - - -
72 83.2 9.1 60.6 50.4 40.3 30.1 - - 74.5 10.0 56.6 46.7 36.8 26.8 - -
67 75.8 9.0 73.7 67.1 56.9 46.8 36.6 - 68.0 9.9 68.0 63.6 53.7 43.8 33.8 -
62 71.3 9.0 71.3 71.3 68.3 58.2 48.1 37.9 65.2 9.9 65.2 65.2 63.4 53.5 43.6 33.6
57 70.8 9.0 70.8 70.8 68.9 58.7 48.6 38.4 64.6 9.9 64.6 64.6 62.9 53.0 43.0 33.1
3000
77 92.0 9.2 55.1 36.8 25.5 - - - 81.9 10.1 55.4 33.2 21.5 - - -
72 84.6 9.1 66.1 54.8 43.5 32.2 - - 75.3 10.1 62.0 50.9 39.9 28.8 - -
67 77.1 9.1 77.1 72.8 61.5 50.2 38.9 - 68.7 10.0 68.7 68.7 58.2 47.1 36.0 -
62 72.5 9.0 72.5 72.5 73.8 62.5 51.2 39.9 65.9 9.9 65.9 65.9 65.9 57.6 46.6 35.5
57 72.0 9.0 72.0 72.0 74.4 63.1 51.8 40.5 65.2 9.9 65.2 65.2 65.2 57.1 46.0 34.9
3375
72 84.3 9.2 70.6 58.4 46.2 34.0 - - 74.8 10.1 66.0 54.1 42.2 30.3 - -
67 76.9 9.1 76.9 74.8 65.3 53.1 41.0 - 68.2 10.0 68.2 68.2 61.6 49.8 37.9 -
62 72.4 9.0 72.4 72.4 73.0 60.8 48.6 36.4 65.4 10.0 65.4 65.4 65.4 55.0 43.1 31.2
57 71.8 9.0 71.8 71.8 73.0 60.8 48.7 36.5 64.8 10.0 64.8 64.8 64.8 54.4 42.5 30.6
3750
72 84.1 9.2 75.1 62.0 48.9 35.9 - - 74.2 10.1 70.0 57.3 44.6 31.9 - -
67 76.7 9.1 76.7 76.7 69.2 56.1 43.0 - 67.7 10.0 67.7 67.7 65.1 52.4 39.7 -
62 72.2 9.1 72.2 72.2 72.2 59.1 46.0 33.0 65.0 10.0 65.0 65.0 65.0 52.3 39.6 26.9
57 71.7 9.0 71.7 71.7 71.7 58.6 45.5 32.5 64.3 10.0 64.3 64.3 64.3 51.6 38.9 26.2
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
XP090 (7.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65