Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
* = Single-phase outdoor units only.
* = Single-phase outdoor units only.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H2RD036S06 , H1RD036S(25,46) **
INDOOR COIL MODEL NO. FC/MC/PC/UC36
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1000 1200 1400
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 35.0 35.7 34.7 38.9 40.5 37.2 37.2 35.8 40.0 41.4 39.3 38.8 36.9 41.1 42.3
S.C. 32.1 30.0 25.0 25.8 19.7 33.8 32.8 27.5 28.1 21.3 35.6 35.7 29.9 30.4 22.9
KW 2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.0 2.1
75
T.C. 33.3 34.2 33.1 37.0 38.7 35.6 35.9 34.3 38.1 39.5 38.0 37.6 35.4 39.1 40.4
S.C. 30.5 29.0 24.3 24.9 19.2 32.3 31.7 26.7 27.2 20.7 34.2 34.4 29.1 29.5 22.3
KW 2.2 2.2 2.2 2.2 2.3 2.2 2.2 2.2 2.2 2.3 2.2 2.2 2.2 2.2 2.3
85
T.C. 31.6 32.6 31.6 35.1 36.8 34.1 34.5 32.8 36.1 37.7 36.6 36.3 34.0 37.1 38.5
S.C. 28.8 28.0 23.5 24.0 18.6 30.8 30.6 25.9 26.4 20.2 32.9 33.2 28.4 28.7 21.8
KW 2.3 2.4 2.4 2.4 2.5 2.4 2.4 2.4 2.4 2.5 2.4 2.4 2.4 2.4 2.5
95
T.C. 29.9 31.1 30.0 33.2 35.0 32.5 33.1 31.3 34.8 35.8 35.2 35.1 32.5 35.1 36.6
S.C. 27.2 27.0 22.7 23.1 18.0 29.3 29.5 25.2 25.4 19.6 31.5 31.9 27.6 27.9 21.2
KW 2.5 2.5 2.5 2.6 2.7 2.5 2.6 2.6 2.6 2.7 2.6 2.6 2.6 2.6 2.7
105
T.C. 28.8 29.5 28.1 31.1 32.6 31.0 31.3 29.2 32.0 33.3 33.3 33.2 30.3 33.0 34.0
S.C. 26.1 25.9 21.7 22.2 17.3 27.9 28.0 24.0 24.5 18.8 29.7 30.1 26.3 26.9 20.4
KW 2.7 2.7 2.7 2.8 2.9 2.7 2.8 2.7 2.8 2.9 2.8 2.8 2.8 2.8 2.9
115
T.C. 27.7 27.9 26.3 29.1 30.4 29.6 29.6 27.2 30.0 30.9 31.5 31.3 28.2 30.9 31.4
S.C. 25.0 24.9 20.7 21.3 16.6 26.5 26.6 22.9 23.6 18.1 28.0 28.4 25.0 25.9 19.6
KW 2.9 2.9 2.9 3.0 3.1 2.9 2.9 2.9 3.0 3.1 3.0 3.0 2.9 3.0 3.1
125
T.C. 26.6 26.3 24.4 27.0 28.1 28.2 27.9 25.3 27.9 28.4 29.7 29.5 26.1 28.8 28.8
S.C. 24.0 23.8 19.8 20.4 15.9 25.1 25.3 21.7 22.7 17.3 26.2 26.7 23.7 25.0 18.8
KW 3.1 3.1 3.0 3.1 3.3 3.1 3.1 3.1 3.2 3.3 3.2 3.2 3.1 3.2 3.3
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
** For three-phase, decrease T.C. by 0.3 and S.C. by 0.2.
Air Handler Coil T.C. S.C. KW
MA12B FC/MC36B 1.00 1.00 1.00
MA12B G*FD036H17 1.00 1.00 1.00
AHP36 1.01 1.07 1.01
AHP42 1.01 1.08 1.01
AHP/SHP60 1.03 1.05 0.99
F*FP040 1.00 1.00 1.00
MV12B* FC/MC36B 1.01 0.98 1.01
MV16C* FC/MC36C 1.01 0.99 0.97
AV36* 1.01 0.99 0.97
AV/SV48* 1.03 0.99 1.00
HC36 1.01 1.01 1.01
HD36 1.03 1.05 1.03
G*FA048S17 1.00 1.00 1.00
G*FA048S21 1.00 1.00 1.00
G*FD036H17 1.00 1.00 1.00
G*FD036H21 1.00 1.00 1.00
G*FD042H21 1.03 1.05 1.03
G*FD046H17 1.00 1.00 1.00
Variable Speed
Furnace *
Coil T.C. S.C. KW
PV8*A12 FC/MC/PC36A 1.01 1.00 1.01
PV9*A12 FC/MC/PC36A 1.00 1.00 1.00
PV8*B16 FC/MC/PC36B 1.01 1.01 1.01
P(C,V)9*B12 FC/MC/PC36B 1.01 1.00 1.01
PV8*C16 FC/MC/PC36C 1.01 1.01 0.97
PV8*C20 FC/MC/PC36C 1.01 1.01 0.97
P(C,V)9*C16 FC/MC/PC36C 1.01 1.01 1.01
P(C,V)9*C20 FC/MC/PC36C 1.01 1.01 0.97
PV8*B16 HC36 1.03 1.05 0.99
P(C,V)9*B12 HC36 1.03 1.04 1.03
PV8*A12 HD36 1.03 1.05 1.03
PV8*B16 HD36 1.03 1.06 0.99
PV8*C16 HD36 1.03 1.06 0.99
PV8*C20 HD36 1.03 1.06 0.99
PV9*A12 HD36 1.03 1.05 1.03
P(C,V)9*B12 HD36 1.03 1.05 0.99
P(C,V)9*C16 HD36 1.03 1.06 0.99
P(C,V)9*C20 HD36 1.03 1.06 0.99