York D3CG Air Conditioner User Manual


 
COOLING CAPACITIES (CFM Air Flow) - 180 UNITS
Air On
Evaporator Coil
To t a l
Cap.
1
MBH
Power
Input
2
kW
Sensible Capacity
1
, MBH
Entering Dry Bulb Temp., °F
CFM
WB °F
90 86 82 79 75 72
@80°F Air Temperature on Condenser Coil1
7200
73 227 14.7 175 151 126 102 78 -
70 213 14.4 200 176 152 127 103 79
66 199 14.0 199 199 177 153 128 104
63 193 14.0 193 193 190 166 142 117
59 188 13.9 188 188 188 176 152 128
5930
73 210 14.5 157 136 115 93 72 -
70 197 14.2 180 159 138 116 95 74
66 184 13.9 184 182 160 139 118 97
63 179 13.8 179 179 172 151 130 109
59 174 13.7 174 174 174 163 142 121
4450
73 195 14.3 127 111 95 79 63 -
70 183 14.0 146 130 114 98 82 66
66 171 13.6 165 149 133 117 101 86
63 166 13.6 166 159 143 127 111 96
59 162 13.5 162 162 153 137 121 105
@95°F Air Temperature on Condenser Coil
7200
73 207 15.9 170 146 122 98 74 -
70 195 15.5 195 171 147 123 99 75
66 183 15.2 183 183 172 148 124 100
63 179 15.1 179 179 179 159 135 111
59 174 15.0 174 174 174 162 138 113
5930
73 192 15.9 150 129 108 87 66 -
70 181 15.6 172 151 130 109 88 67
66 170 15.2 170 170 153 132 110 89
63 166 15.1 166 166 162 141 120 99
59 161 15.0 161 161 161 151 130 109
4450
73 177 15.6 123 107 91 75 59 -
70 167 15.3 142 126 110 94 78 62
66 157 14.9 157 145 129 113 97 81
63 153 14.8 153 153 137 121 105 89
59 149 14.7 149 149 145 129 113 97
@115°F Air Temperature on Condenser Coil
7200
73 169 18.2 157 133 109 85 61 -
70 161 17.6 161 158 134 110 85 61
66 154 17.1 154 154 154 135 110 86
63 149 17.1 149 149 149 137 112 88
59 144 17.1 144 144 144 132 107 83
5930
73 169 17.8 141 120 99 78 57 -
70 161 17.2 161 142 121 100 79 58
66 153 16.6 153 153 144 123 102 81
63 148 16.6 148 148 148 128 107 86
59 143 16.6 143 143 143 133 112 90
4450
73 159 17.5 114 98 82 66 50 -
70 151 17.0 133 117 101 85 69 53
66 144 16.4 144 136 120 104 88 72
63 139 16.4 139 139 124 108 92 76
59 135 16.4 135 135 128 112 96 80
1
These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the
supply air blower motor.
2
These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.
530.26-TG3YI
Unitary Products Group 5