UNIT
SIZE
POWER
SUPPLY
COMPRESSOR
OUTDOOR
FAN
MOTOR,
(#1 & #2)
FLA, EACH
SUPPLY AIR
BLOWER
MOTOR, (FLA)
TOTAL UNIT
AMPACITY,
(AMPS)
MAX.
FUSE
SIZE
1
MIN.
WIRE SIZE
2
,
(mm
2
/AWG)RLA LRA
3 kW
4 HP
5.6 kW
7.5 HP
3 kW
4 HP
5.6 kW
7.5 HP
#1 #2 #1 #2
180 380/400/415-3+N-50 19.2 9.6 146 73 2.4 8.6 - 47.0 - 60 10 / 8
240 380/400/415-3+N-50 19.2 19.2 146 146 2.4 - 11.7 - 59.7 70 16 / 6
NOTES: 1. Slow blow type fuse.
2. Based on 105°C insulated copper conductors in conduit.
24 VOLT
TRANSFORMER
ELECTRICAL DATA - Cooling Only Units and Units With Gas Heat
FIELD WIRING - Electric/Electric and Gas/Electric Units
GRD. LUG
LINE VOLTAGE
TERMINAL
BLOCK 2TB
IN UNIT
CONTROL BOX
L1
L2
L3
N
NEUTRAL
TERMINAL
Refer to the
ELECTRICAL DATA
tables to size the
power wiring, the fuses and
the disconnect switch.
530.26-TG3YI
Unitary Products Group 13