York D3CG Air Conditioner User Manual


 
BLOWER
SPEED,
RPM
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
5930 CFM 6990 CFM 8050 CFM 8685 CFM 9320 CFM
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
765 6.00.82.82.40.33.63.1---------
795 5.01.03.02.60.53.83.3---------
820 4.01.13.22.70.64.03.4---------
850 3.01.23.42.90.84.33.70.25.34.5------
875 2.01.33.63.00.94.53.80.35.54.7------
905 1.0 1.5 3.8 3.2 1.1 4.8 4.1 0.5 5.8 5.0 0.1 6.5 5.5 - - -
STANDARD DRIVE (CFM)
BLOWER
SPEED,
RPM
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
5930 CFM 6990 CFM 8050 CFM 8685 CFM 9320 CFM
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
895 6.0 1.5 3.7 3.2 1.0 4.7 4.0 0.5 5.7 4.9 0.1 6.3 5.4 - - -
925 5.0 1.6 3.9 3.4 1.2 4.9 4.2 0.6 6.0 5.1 0.3 6.7 5.7 - - -
955 4.0 1.8 4.2 3.6 1.3 5.2 4.4 0.8 6.3 5.4 0.4 7.0 6.0 0.1 7.8 6.6
990 3.0 2.0 4.4 3.8 1.5 5.5 4.7 1.0 6.7 5.7 0.7 7.4 6.3 0.3 8.2 7.0
1020 2.0 2.1 4.7 4.0 1.7 5.8 5.0 1.2 7.0 6.0 0.9 7.8 6.7 0.5 8.6 7.3
1050 1.0 2.3 4.9 4.2 1.9 6.1 5.2 1.4 7.4 6.3 1.0 8.2 7.0 - - -
1080 0.0 2.5 5.2 4.4 2.1 6.4 5.5 1.6 7.7 6.6 1.2 8.5 7.3
NOTES: 1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat.
2. Refer to Page 12 for the resistance values for all other unit options or applications.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.
*Do NOT close pulley below minimum turns open.
HIGH SPEED DRIVE (CFM)
BLOWER
SPEED,
RPM
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
2.80 m
3
/s 3.30 m
3
/s 3.80 m
3
/s 4.10 m
3
/s 4.40 m
3
/s
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
765 6.02022.12.4802.73.1- -------
795 5.02382.32.61172.93.3---------
820 4.02682.42.71503.03.4---------
850 3.03052.52.91893.23.7503.94.5------
875 2.03362.73.02223.43.8854.14.7------
905 1.0 347 2.8 3.2 262 3.6 4.1 128 4.3 5.0 37 4.8 5.5 - - -
STANDARD DRIVE (m /s)
3
BLOWER
SPEED,
RPM
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
2.80 m
3
/s 3.30 m
3
/s 3.80 m
3
/s 4.10 m
3
/s 4.40 m
3
/s
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
895 6.0 361 2.8 3.2 249 3.5 4.0 114 4.3 4.9 22 4.7 5.4 - - -
925 5.0 400 2.9 3.4 290 3.7 4.2 157 4.5 5.1 66 5.0 5.7 - - -
955 4.0 439 3.1 3.6 332 3.9 4.4 201 4.7 5.4 112 5.2 6.0 15 5.8 6.6
990 3.0 486 3.3 3.8 381 4.1 4.7 254 5.0 5.7 166 5.5 6.3 70 6.1 7.0
1020 2.0 527 3.5 4.0 425 4.3 5.0 299 5.2 6.0 213 5.8 6.7 119 6.4 7.3
1050 1.0 569 3.7 4.2 469 4.6 5.2 346 5.5 6.3 261 6.1 7.0 - - -
1080 0.0 612 3.9 4.4 514 4.8 5.5 393 5.8 6.6 310 6.4 7.3 - - -
HIGH SPEED DRIVE (m /s)
3
BLOWER PERFORMANCE (D*CG240 UNIT SUPPLY AIR) -
w/DOWNFLOW DUCT APPLICATIONS
530.26-TG3YI
Unitary Products Group 11