York D3CG Air Conditioner User Manual


 
RATINGS
®
SUNLINE 2000
MODEL DCG
(Gas Heating)
(OPTION / ACCESS.) DCE UNITS
D*CG UNITS
(OPTION / ACCESSORY)
THROWAWAY
ALUMINIZED STEEL
FEMALE
Model
Rating
1
Point
Total Output,
Mbh / kW
Total Input,
kW
COP
2
EER
3
Sensible Output,
Mbh / kW
Latent Output,
Mbh / kW
Electric Heat4
Nominal Capacity,
kW
D3CE180
T1 159 / 46.6 18.2 2.60 8.80 132 / 38.7 26.9 / 7.9
T2 142 / 41.7 20.0 2.10 7.15 141 / 41.2 1.6 / 0.5 18, 36, 54, 72
T3 152 / 44.6 16.4 2.75 9.40 119 / 34.9 33.2 / 9.7
D3CE240
T1 210 / 61.5 24.8 2.50 8.50 176 / 51.5 34.0 / 10.0
T2 182 / 53.3 27.1 2.00 6.75 182 / 53.3 0.0 / 0.0 18, 36, 54, 72
T3 196 / 57.5 22.2 2.60 8.80 152 / 44.6 42.6 / 12.5
1
T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.
2
COP = Coefficient of Performance - total output kW divided by the total input kW.
3
EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.
4
Heaters available as factory-installed options or field-installed accessories - all with single point power supply.
CAPACITY RATINGS - Cooling / Electric Heating
Model
Cooling Capacity,
Mbh / kW
Gas Heat Capacity
Input (Net)
Mbh / kW
Output
Mbh / kW
Gas Rate*
cfh / m
3
/h
Temp. Rise (°F / °C)
At Full Input
Min. Max.
D3CG180N320 180 / 52.7
291 / 85.2 258 / 75.6 302 / 8.5 30 / 17 60 / 33
D3CG240N320 240 / 70.3
NOTE: Gas Heaters are shipped available for natural gas, but can be converted to L.P. / propane gas with a field-installed conversion accessory. All gas units are two-stage heating.
First stage is 50% of total.
*Based on net input and 2nd. -H family, G20 (methane) net fuel value (9.97 kWh/m
3
).
CAPACITY RATINGS - Gas Heating
530.26-TG3YI
Unitary Products Group 3