York D2EB030 Air Conditioner User Manual


 
360101-XTG-B-0508
Johnson Controls Unitary Products 5
EER = Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric
power input in watt-hours during the same period.
TABLE 1: PHYSICAL DATA
MODELS
DEB
030 036 042 048 060
EVAPORATOR
BLOWER
CENTRIFUGAL BLOWER (Dia. x Wd. in.) 10 X 8 10 x 8 11 X 10 11 x 10 11 x 10
FAN MOTOR HP ½ 1
EVAPORATOR
COIL
ROWS DEEP 22223
FINS PER INCH 15 15 15 13 16
FACE AREA (Sq. Ft.) 4.38 4.38 4.38 5.62 5.26
CONDENSER
FAN
PROPELLER DIA. (in.) 22 22 22 22 22
FAN MOTOR HP 1/4 1/4 1/4 1/4 1/4
NOM. CFM TOTAL 2,400 2,400 2,400 2,800 2,800
CONDENSER
COIL
ROWS DEEP 11111
FINS PER INCH 20 18 16 13 20
FACE AREA (Sq. Ft.) 8.3 8.3 11.7 16.4 16.4
CHARGE REFRIGERANT 22 (lbs./oz.) 3 / 13 3 / 10 4 / 8 5 / 15 5 /15
FILTER FACE AREA (Sq. Ft.) / Qty. / Size 2.14 / 2 / 14" x 22"
COMPRESSOR HERMETIC, QTY. = 1 (Type) Recip. Recip. Recip. Scroll Scroll
3
4
3
4
3
4
TABLE 2: RATINGS - ARI
Model DEB
Cooling Capacity
1
80/67-95 °F Sound Rating
2
(decibels)
Electric Heat
Nom. Capacity
KW
(single phase)
Electric Heat
Nom. Capacity
KW
(three phase)MBH EER
030 29.0 8.9 79 5.0, 7.5, 10.0, 15.0 -
036 35.2 8.7 81 5.0, 7.5, 10.0, 15.0 10.0, 15.0
042 40.5 9.4 83 5.0, 7.5, 10.0, 15.0 10.0, 15.0
048 46.5 8.8 81 10.0, 15.0, 20.0, 25.0 10.0, 15.0, 20.0, 25.0
060 59.0 8.8 79 10.0, 15.0, 20.0, 25.0 10.0, 15.0, 20.0, 25.0
1. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/
240.
2. Rated in accordance with ARI Standard 270.