York 036-21103-003 Air Conditioner User Manual


 
036-21103-003 Rev. A (0403)
Unitary Products Group 7
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA018S78A
INDOOR COIL MODEL NO. G2FD024S17
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 500 650 800
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
75
T.C. 18.3 18.1 16.5 18.4 18.2 17.2 18.4 18.3 17.8
S.C. 10.6 10.8 10.5 11.0 11.6 11.9 11.4 12.4 13.3
K.W 1.55 1.55 1.53 1.71 1.71 1.69 1.68 1.67 1.66
85
T.C. 17.8 17.2 15.4 18.0 17.5 16.1 18.2 17.8 16.8
S.C. 10.6 10.7 10.2 11.3 11.7 11.6 12.0 12.8 13.1
K.W 1.76 1.74 0.95 1.95 1.93 1.90 1.95 1.93 1.90
95
T.C. 17.3 16.3 14.2 17.6 16.8 15.0 17.9 17.3 15.8
S.C. 10.6 10.5 9.8 11.6 11.8 11.4 12.5 13.1 12.9
K.W 1.79 1.75 1.71 1.95 1.92 1.88 1.92 1.89 1.85
105
T.C. 16.0 14.7 12.6 16.5 15.3 13.3 17.0 15.9 14.1
S.C. 10.0 10.0 9.2 11.4 11.4 10.7 12.7 12.8 12.2
K.W 1.99 1.94 1.90 2.19 2.14 2.09 2.19 2.14 2.09
115
T.C. 14.6 13.1 11.0 15.3 13.8 11.7 16.0 14.4 12.3
S.C. 9.4 9.5 8.5 11.2 11.0 10.0 12.9 12.5 11.5
K.W 2.01 1.94 1.90 2.18 2.12 2.07 2.16 2.10 2.04
125
T.C. 13.0 11.1 9.3 13.7 11.6 9.9 14.3 12.1 10.4
S.C. 9.4 8.5 7.8 11.1 10.0 9.2 12.7 11.5 10.6
K.W 2.11 2.04 1.98 2.28 2.21 2.15 2.26 2.19 2.13
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
N1AHB1293 G2FD024S17 1.00 1.00 1.00
F2RP024N93 1.00 1.00 1.00