036-21103-003 Rev. A (0403)
Unitary Products Group 13
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA060S50A
INDOOR COIL MODEL NO. G*FD060S24A
CONDENSER
ENTERING AIR
TEMPERATURE
IDCFM 1650 1900 2150
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
75
T.C. 65.0 62.4 59.6 65.8 62.8 60.0 66.6 63.3 60.5
S.C. 41.8 41.5 41.0 44.7 44.0 43.6 47.5 46.5 46.1
K.W 5.40 5.36 5.28 5.81 5.76 5.69 5.62 5.56 5.50
85
T.C. 63.9 60.7 56.5 64.7 61.4 57.5 65.4 62.1 58.5
S.C. 41.8 41.1 39.8 44.7 43.7 42.5 47.5 46.4 45.3
K.W 6.11 6.04 5.91 6.57 6.49 6.38 4.41 4.34 4.27
95
T.C. 62.8 59.1 53.5 63.5 60.0 55.0 64.3 60.8 56.5
S.C. 41.8 40.7 38.6 44.6 43.5 41.5 47.5 46.2 44.4
K.W 6.21 6.12 5.94 6.63 6.53 6.39 6.45 6.33 6.23
105
T.C. 60.6 55.3 49.3 61.5 56.6 50.7 62.4 58.0 52.2
S.C. 40.9 39.4 36.8 44.0 42.4 39.8 47.1 45.3 42.9
K.W 6.92 6.74 6.57 7.38 7.22 7.05 7.24 7.10 6.93
115
T.C. 58.5 51.5 45.1 59.6 53.3 46.5 60.6 55.1 47.9
S.C. 40.1 38.2 35.0 43.4 41.3 38.2 46.8 44.4 41.4
K.W 7.03 6.76 6.59 7.44 7.22 7.02 7.25 7.08 6.84
125
T.C. 52.9 47.7 40.4 54.2 48.5 41.9 55.5 49.4 43.5
S.C. 38.7 36.7 32.8 42.0 39.4 35.8 45.4 42.1 38.9
K.W 7.31 7.09 6.84 7.78 7.53 7.29 7.64 7.36 7.13
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
NAHD2093 G2FD060S24 1.00 1.00 1.00
F2RP060N93 1.00 1.00 1.00