York 036-21103-003 Air Conditioner User Manual


 
036-21103-003 Rev. A (0403)
10 Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA036S50A
INDOOR COIL MODEL NO. G2FD036S17
CONDENSER
ENTERING AIR
TEMPERATURE
IDCFM 1100 1250 1400
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
75
T.C. 38.6 36.0 33.4 39.0 36.4 33.9 39.4 36.8 34.3
S.C. 26.0 25.7 25.3 25.8 26.4 27.1 25.6 27.2 28.8
K.W 3.20 3.12 3.04 3.30 3.34 3.38 2.99 3.15 3.31
85
T.C. 36.4 33.7 31.0 36.9 34.2 31.4 37.5 34.7 31.9
S.C. 24.8 24.5 24.2 25.2 25.5 25.9 25.5 26.5 27.5
K.W 3.56 3.48 1.88 3.75 3.75 3.75 3.53 3.61 3.69
95
T.C. 34.2 31.3 28.5 34.8 31.9 28.9 35.5 32.5 29.4
S.C. 23.6 23.3 23.0 24.5 24.6 24.7 25.4 25.9 26.3
K.W 3.52 3.44 3.36 3.74 3.70 3.66 3.55 3.55 3.55
105
T.C. 31.9 29.0 26.0 32.8 29.6 26.5 33.6 30.3 27.0
S.C. 22.5 22.2 21.9 23.9 23.7 23.5 25.3 25.2 25.1
K.W 3.88 3.80 3.72 4.19 4.11 4.03 4.09 4.01 3.93
115
T.C. 29.7 26.6 23.5 30.7 27.4 24.0 31.7 28.1 24.5
S.C. 21.3 21.0 20.7 23.2 22.8 22.3 25.2 24.5 23.9
K.W 3.84 3.76 3.68 4.18 4.06 3.94 4.11 3.95 3.79
125
T.C. 27.6 24.3 21.0 28.1 24.9 21.7 28.6 25.5 22.4
S.C. 20.6 20.0 19.4 22.7 21.6 20.5 24.8 23.2 21.7
K.W 3.92 3.92 3.92 4.38 4.26 4.14 4.43 4.19 3.95
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
NAHB1293 G2FD036S17 1.00 1.00 1.00
NAHB1293 G2FD036S21 1.02 1.02 1.02
NAHC1693 G2FD042S21 1.04 1.04 1.03
F2RP036N93 1.02 1.02 1.02