White Rodgers 1F95CA-391 Heat Pump User Manual


 
INSTALLER TABLE
NOTE: You must be in the User Configuration Menu to enter the Installer Table. Firmly press TIME
FWD
and
TIME
BACK
at same time and release to enter the Configuration Menu.
6
1 MLTI STG HEAT PUMP
2 HEAT PUMP
(1)
2
Selects type of system. Selecting HEAT PUMP
makes additional items for heat pump systems
available.
3 ELEC HEAT FAN
(ON)
OFF
Fan cycles with call for heat if ON. Fan always
cycles with pump stages.
4
1 to 40 for multi-stage
9 to 40 for heat pump
5
9 to 40
12
(Balance point temperature)
bPT (35 F)
5 F to 50 F
15
17
COMP LOCK
(OFF)
ON
HEAT-OFF COOL-AUTO
or HEAT-EMER-OFF-
COOL-AUTO
(for heat pumps)
HEAT-OFF-COOL or
HEAT-EMER-OFF-
COOL (for heat pumps)
Returns to Normal Operation.
13
14 (Programmable Blower
Balance Point) bbP
(OFF)
10 to 99%
Available if configured for HEAT PUMP. Adjustable
from 99-10. Lowers the Blower speed if the Heat
Pump duty cycle is above the selected value in
percentage.
1. One compressor on Y1.
2. Two compressor on Y1, Y2.
Selects HEAT anticipation adjustment.
Selects COOL anticipation adjustment.
Available if Pump (Step 10) is OFF and OUTDOOR
Sensor OFF. The higher the number the sooner the
auxilary stage energizes. The lower the number the
longer period of time before auxiliary is energized.
Available if Pump (Step 10) is OFF and OUTDOOR
Sensor ON. Selects outdoor balance point
temperature for Heat Pump.
Selects compressor short-cycle protection.*
Allows selection of HEAT and COOL or HEAT,
COOL and AUTO with SYSTEM button. (EMER
appears in sequence after HEAT if HEAT PUMP
is selected).
Program RUN
TIME FWD
(Heat Pump ONLY)
TIME FWD
TIME FWD
TIME FWD
TIME FWD
TIME FWD
TIME FWD
TIME FWD
6 SET CYCL AUX
(08)
1 to 40
9 HEAT FAN DELA OFF
(00)
0 to 127 seconds
10 PUMP
(ON)
OFF
11 COMP OFF DELA
(60)
(0) to (99)
7 COOL FAN DELA OFF
(00)
0 to 127 seconds
8
5
5
5
5
5
5
5
5
7
7
7
7
7
7
5
5 FAN DELA ON
(01)
1 to 30 seconds
Selects time delay for fan ON. Applies only to
compressor stages for heat pump or COOL.
Selects time delay for COOL fan OFF.
Selects AUXILIARY stage anticipation adjustment.
(Heat Pump ONLY)
Selects time delay for fan ON only when
ELECT HEAT FAN (Step 3) is ON.
Fossil Fuel Kit Alternative option. Turns compressor
OFF if Auxiliary is ON for longer than one minute.
(Heat Pump 1 & 2)
Available if Pump (Step 10) is OFF. Selects the
delay between de-energizing fossil fuel stage and
restarting Heat Pump stage.
TIME FWD
(Heat Pump ONLY)
TIME FWD
(Heat Pump ONLY)
TIME FWD
TIME FWD
TIME FWD
TIME FWD
Step Press Button(s) Displayed (Factory Default) Press UP or DOWN to select: COMMENTS
See
Page
SET CYCL (05)
for MLTI_STG, (13) for
HEAT PUMP 1, (24)
for HEAT PUMP 2
SET CYCL (24)
for MLTI_STG, (13) for
HEA
T
PUMP 1, (24)
for HEAT PUMP 2
(Heat Pump ONLY)
TIME FWD
(Heat Pump ONLY)
(Heat Pump ONLY)
(Heat Pump ONLY)
(Balance point)
bP (05)
(01) to (09)
* Note: COMP LOCK OFF permanently defeats compressor lockout. You must turn this selection ON if you do not have a system that already provides
compressor short-cycle protection. Please see Lockout Bypass Option to temporarily override compressor lockout.
Firmly Press
SET TIME and
SET DAY (hold
for approx. 3 seconds)
16
TIME FWD
ON
7
CA
(OFF)
Selects active Comfort Alert. Requires CA module
and CA interface module.