WhisperKool 081310 Air Conditioner User Manual


 
Page 6 GSM-01 081310
General Installation Guidelines and Instructions
WhisperKOOL requires that a certied HVAC technician install and charge all split systems. Please take a
moment to review state and city building codes to ensure the safe and proper installation of the system.
Electrical Needs
WhisperKOOL split systems requires a dedicated 110-volt 20-amp circuit. The system draws a large amount
of amps at initial start up. By designating a dedicated circuit breaker, you will guarantee that the system has
enough power to run eectively. Contact an electrician for assistance with the installation of this dedicated
electrical circuit:
1. Match the electrical outlet to the plug provided on the WhisperKOOL unit.
2. Provide a dedicated circuit and wiring for the unit.
3. Provide a weatherproof plug for units mounted outside.
WE RECOMMEND THAT YOU DO NOT USE A GROUND FAULT INTERRUPTER (GFI) WITH THIS PRODUCT.
In case the system should lose power, press the reset button and attempt to turn the unit back on. Check
the home/main circuit breaker. If the unit does not respond properly, refer to the Troubleshooting section
on
page 17.
Condensing Unit Preparation
Note: The condensing unit is shipped with a protective foam pad/ block to prevent damaging tubing
against the condenser coil ns. Please ensure that this pad is removed prior to operation.
SPLIT SYSTEM INSTALLATION
*A Low Ambient Control is used on most models,
a Fan Cycling Switch is used otherwise.