CGs-4E Gas-Fired Water Boiler — Boiler Manual
Failure to prevent low return water temperature to the boiler could cause corrosion of
the boiler sections or burners, resulting in severe personal injury, death or substantial
property damage.
Radiant heating system piping should include a means of regulating the boiler return
water temperature
and the system supply temperature (such as provided by an injec-
tion pumping control
).
Boilerreturnwatertemperaturewillbeadequatelycontrolledusingthemethodsshown
in this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods of this manual if the system is equipped with an outdoor
reset control.
Instead, provide controls and piping which can regulate the boiler re-
turn water temperature
at no less than 130°F regardless of system supply temperature.
ContactyourWeil-McLainrepresentativeforsuggestedpipingandcontrolmethods.
Failure to prevent cold return water temperature to the boiler could cause corrosion
damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.
3d Piping — low temp systems (continued)
BOILER-bypass piping
method
This piping method (Figures 10 and 11, page 21) is
called a boiler-bypass because part of the circulator
flow is bypassed around the boiler (through valve 7a).
This method reduces the flow rate throughout the boiler,
in order to raise the average water temperature in the
boilerenoughtopreventuegascondensation.Boiler-
bypass piping is effective for some boilers — including
theCGs-4E—providedtheowratesareadjusted
according to the instructions following.
Figures 10 and 11 are alternative piping suggestions
for converted gravity (large water content or steam
systems) or radiant heating system — for use when
primary/secondary piping can’t be applied. (Figure 12,
page 23, is another alternative, using system bypass in
place of boiler-bypass piping. Figure 12 however, is
not suitable for radiant heating applications because it
does not protect the radiant system from possible high
water temperature.)
Boiler-bypasspipingkeepssystemowrateashighas
possible and temperature drop as low as possible, help-
ing to equalize the building heat distribution.
Temperature gauges
Gauge4a is optional if the bypass valves will be ad-
justed using cold (or room temperature) return water
to the boiler. (When setting the valves without gauge
4a installed — using cold or room temperature water
—assumethereturnwatertemperaturetobe60°F.Set
the valves so gauge 8readsatleast120°F.
Gauge
4b is optional on converted gravity systems,
but required on radiant heating systems — to display
the water temperature being supplied to the radiant
tubing.
Gauge
8 is required on all systems to assure reliable
adjustment of the bypass valves. The boiler-mounted
temperature/pressure gauge can be used if a separate
temperature gauge is not installed.
Valve adjustment
1. Startwithvalve7a fully closed and 7b fully open.
2. Graduallyopenvalve
7a while closing valve 7b
until the temperature at gauge 8 reads60°Fhigher
than gauge 4a.Aminimum60°Ftemperaturerise
through the boiler assures a low enough flow rate
and high enough average temperature to prevent
condensation even with low system return water
temperature.
3. Valve
7a regulates the system flow rate, while valve
7b regulates the boiler flow rate.
4. The boiler-mounted temperature/pressure gauge
may be used in place of a separate gauge
8.