CGs-4E Gas-Fired Water Boiler — Boiler Manual
Water piping — single-zone system3b
Figure 4 Diaphragm- or bladder-type expansion tank
Piping to single-zone system
See Table 3 for piping sizes.
Figure 5 Closed-type expansion tank
Piping to single-zone system
See Table 3 for piping sizes.
Diaphragm-type or bladder-
type expansion tank (Figure 4)
1. Ensureexpansiontanksizewillhandleboilerand
system water volume and temperature. Tank must
be located in boiler return piping as close to boiler
aspossible,beforeinletsideofcirculator.Seetank
manufacturer’s instructions for details.
2. Install an
automatic air vent in air vent tapping as
shown.
Closed-type expansion tank
(Figure 5)
1. Ensureexpansiontanksizewillhandleboilerand
systemwatervolumeandtemperature.Seetank
manufacturer’s instructions for details.
2. Connecttankto½”NPTtappinglocatedbehind
supplyoutlet,using½”NPTpiping.Pitchany
horizontal piping up towards tank 1 inch per 5 feet
of piping.
Undersized expansion tanks cause system water to be lost from relief valve and makeup water
tobeaddedthroughllvalve.Eventualsectionfailurecanresult.
Use Figure 4 or Figure 5 onlyforsingle-zonesystemsdesignedforreturnwateratleast130°F.
For systems with low return water temperature possible, such as converted gravity systems
and radiant heating systems, refer to the special piping suggestions of pages 18-23. Failure to
prevent low return water temperature to the boiler could cause corrosion of the boiler sections
or burners, resulting in severe personal injury, death or substantial property damage.