BCP-3 Installation and Operation Manual
Button and Navigating Menus
The BCP-3 has three buttons.
The SET button function varies. When the Default Screen is
displayed, pressing the SET Button views the MENU. When
in the Menus and settings, the SET Button accepts the selected
entry or setting value.
When in the menus, pressing the Up and Down buttons will
scroll through the menu options. They can be used to change
the setting of a specific function. I.e., change the Set Point,
Differential, or System Trim. In addition, when in the default
screen, the Up and Down buttons will display the outdoor
temperature and Outdoor Cutoff.
At the end of every operation menu there is a <Back> option
that allows the user to go back one menu level. If the SET
Button was held down for three seconds on the <Back>
option, the display will go back to the default screen.
SE
SE
T
T
DISPLAY UNIT:
F
C
SENSOR FAULT:
Output On
Output Off
CONTROL MODE:
Outdoor Reset
Set Point
OUTPUT MODE:
1-On/Off+1-Pump
1-On/Off+2-Pump
2-On/Off+1-Pump
1-Lo/Hi+1-Pump
3-On/Off
Startup Options
When the control is initiated for the first time or after a manual
reset, it will start its operation with the Startup Menu. Later, the
Startup menu can be accessed as an option from the operation
menu. An option must be accepted in each screen in the Startup
Menu to move to the next level.
Display Unit
Options: ºF, ºC Default: ºF
SET
SET
/<System Startup>/Display Unit
The BCP-3 will offer two different temperature display standards. If ºF is selected, all
temperatures will display in Fahrenheit. If ºC is selected, all temperatures will display in Celsius.
DISPLAY UNIT:
F
C
Control Mode
Options: Outdoor Reset, Set Point Default: Outdoor Reset
SET
SET
/<System Startup>/Display Unit/Control Mode
The new BCP-3 has two heating logics. Outdoor Reset; varies the system set point/target
based on outdoor temperature. This selection adds several menu options to adjust and fine tune
the reset curves: Reset Ratio, Offset, Min Water temp, Max Water temp, and Outdoor Cutoff. In
addition, a customized reset ratio curve will be available for specialized applications.
Set Point; gives the installer the flexibility of selecting a fixed set point. The Outdoor Cutoff will
be available if an outdoor sensor was installed.
CONTROL MODE:
Outdoor Reset
Set Point
Output Mode
Options: 1-On/Off+1-Pump, 1-On/Off+2-Pump, 2-On/Off+1-Pump, 3-On/Off
Default: 2-On/Off+1-Pump
SET
SET
/<System Startup>/Display Unit/Control Mode/Output Mode
The new BCP-3 has multiple operating Output Modes of heating. Each can be applied based on
the number of boilers, stages, and pumps controlled. See Output Mode Table on page 4.
OUTPUT MODE:
1-On/Off+1-Pump
1-On/Off+2-Pump
2-On/Off+1-Pump
1-Lo/Hi+1-Pump
3-On/Off
Sensor Fault
Options: Output On, Output Off Default: Output On
SET
SET
/<System Startup>/..../Sensor Fault
The Sensor Fault will determine the operating status of the output relays when a sensor reads
Short or Open. On sensor fault, the Set Point will indicate FAULT TGT=ON or OFF to
indicate the condition of the output and the faulty sensor will read OPEN or SHORT to indicate
the condition of the sensor.
SENSOR FAULT:
Output On
Output Off