Weil-McLain BCP-3 Boiler User Manual


 
6
BCP-3 Installation and Operation Manual
T1
T2
COM
COM
T3+
T3-
EXT+
EXT-
P+
P-
COM
24VAC
System Sensor
Outdoor Sensor
Enable Dry Contact
Setback Timer
120 VAC
Wiring 1 Lo/Hi Boiler +
System Pump
System Pump
(Yellow/Output 1)
Boiler Lo
(Blue/
Output 2)
Boiler Hi
(White/
Output 3)
DHW Call
Power (Black)
120 VAC
L
N
L
N
T1
T2
COM
COM
T3+
T3-
EXT+
EXT-
P+
P-
COM
24VAC
System Sensor
Outdoor Sensor
Enable Dry Contact
Setback Timer
Boiler
(Blue/
Output 2B)
Output capped
(White/Output 3)
Wiring 1 On/Off Boiler +
System Pump
DHW Call
Power (Black)
120 VAC
L
N
120 VAC
L
N
System Pump
(Yellow/Output 1)
T1
T2
COM
COM
T3+
T3-
EXT+
EXT-
P+
P-
COM
24VAC
System Sensor
Outdoor Sensor
Enable Dry Contact
Setback Timer
DHW Call
DHW Pump (White/Output 3)
Boiler
(Blue/
output 2)
Wiring 1 On/Off Boiler +
System Pump + DHW Pump
Power (Black)
120 VAC
L
N
System Pump
(Yellow/Output 1)
120 VAC
L
N
T1
T2
COM
COM
T3+
T3-
EXT+
EXT-
P+
P-
COM
24VAC
System Sensor
Outdoor Sensor
Enable Dry Contact
Setback Timer
Wiring 2 On/Off Boilers +
System Pump
Boiler1
(Blue/
Output 2)
Boiler2
(White/
Output 3)
DHW Call
Power (Black)
120 VAC
L
N
120 VAC
L
N
System Pump
(Yellow/Output 1)
T1
T2
COM
COM
T3+
T3-
EXT+
EXT-
P+
P-
COM
24VAC
System Sensor
Outdoor Sensor
Enable Dry Contact
Setback Timer
Wiring 3 On/Off Boilers
Boiler 2
(Blue/
Output 2)
Boiler 3
(White/
Output 3)
Boiler 1
(Yellow/
Output 1)
DHW Call
Power (Black)
120 VAC
L
N
Boiler
SYS
Pump
DHW
Pump
SET
SET
SYSTEM = 147F
TARGET = 150F
Boiler
SYS
Pump
DHW
Pump
SET
SET
SYSTEM = 147F
TARGET = 150F
Boiler
SYS
Pump
DHW
Pump
SET
SET
SYSTEM = 147F
TARGET = 150F
Boiler
SYS
Pump
DHW
Pump
SET
SET
SYSTEM = 147F
TARGET = 150F
Boiler
SYS
Pump
DHW
Pump
SET
SET
SYSTEM = 147F
TARGET = 150F
BCP-3
BCP-3 BCP-3
BCP-3BCP-3
Output 1 Output 2 Output 3 Output 1 Output 2 Output 3
Output 1 Output 2 Output 3 Output 1 Output 2 Output 3
Output 1 Output 2 Output 3
BCP-3 Output Modes Wiring
NOTES:
The BCP-3 does not source any output power
to any of its relays. A power source must sup-
ply the pumps with power and the control can
break the hot leg.
Weil McLain recommends not sharing the
power source to the control with any pumps,
boilers, or heavy electric equipment.
When wiring a sensor to the BCP-3, connect
the Shield to the COM terminal on the BCP-3
end. DO NOT connect the Shield at the sensor
end.
Eventhough in some Output Modes the BCP-3
does not control the DHW Pump, a DHW call
will raise the System Target to whichever is
lower of 200F or the Maximum Water Temp.