TYPICAL BULK PROPANE GAS SUPPLY INSTALLATION
We recommend that this installation be done by a LICENSED professional.
General Specifications for Piping
Note - Contact your local municipality for building codes regulating outdoor gas grill
installations. In absence of Local Codes, you must conform to the latest edition of the
National Fuel Gas Code ANSI Z223.1/NFPA 54.
This grill is designed to operate at 11 inches of water column pressure. An LP in
line regulator may be necessary for this pressure.
ƽ CAUTION: If young children are in the area, a
locking valve should be considered.
Pipe compound should be used which is resistant to the action of liquid propane
gas when gas connections are made.
The gas connections must be firmly attached to rigid, permanent construction.
Note: The information provided in this manual is general for typical installations. We
cannot cover all possible installation ideas. We recommend, prior to installation, that you
contact your municipality for local building codes and your local fire department for
installation verification.
If you have any questions, contact Customer Service at 1-800-446-1071.
GAS LINE PIPING
Refer to the piping chart at the bottom of previous page.
The corrugated gas line from the manifold is 58 inches (1,473.2 mm) long. Do not
extend the gas line.
We have provided the means to make an SAE 45° flare connection. Do not use
pipe sealant on this connection.
If the length of line required does not exceed 50 feet, use a 5/8” O.D. tube. One
size larger should be used for lengths greater than 50 feet. Refer to piping chart.
Gas piping may be copper tubing, type K or L; polyethylene plastic tube, with a
minimum wall thickness of .062 inch (1.57 mm); or standard weight (schedule 40)
steel or wrought iron pipe.
Copper tubing must be tin-lined if the gas contains more than 0.3 grams of
hydrogen sulfide per 100 cubic feet of gas.
Plastic tubing is suitable only for outdoor, underground use.
Gas piping in contact with earth, or any other material which may corrode the
piping, must be protected against corrosion in an approved manner.
Underground piping must have a minimum of 18” cover.
Table
6.2(a)
Maximum Capacity of Metallic Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 2 psi or Less and
a Pressure Drop of 0.3 Inch Water Column. (Based on a 0.60 Specific Gravity Gas)
Nominal
Iron Pipe
Size
(Inches)
Actual
ID:
(Inches)
Length of Pipe (Feet)
10 20 30 40 50 60 70 80 90 100 125 150 175 200
1/2 .622 131 90 72 62 55 50 46 42 40 38 33 30 28 26
3/4 .824 273 188 151 129 114 104 95 89 83 79 70 63 58 54
1 1.049 514 353 284 243 215 195 179 167 157 148 131 119 109 102
1 1/4 1.380 1,060 726 583 499 442 400 368 343 322 304 269 244 224 209
1/12 1.610 1,580 1,090 873 747 662 600 552 514 482 455 403 366 336 313
2 2.067 3,050 2,090 1,680 1,440 1,280 1,160 1,060 989 928 877 777 704 648 602
2 1/2 2.469 4,860 3,340 2,680 2,290 2,030 1,840 1,690 1,580 1,480 1,400 1,240 1,120 1,030 960
3 3.068 8,580 5,900 4,740 4,050 3,590 3,260 3,000 2,790 2,610 2,470 2,190 1,980 1,820 1,700
4 4.026 17,500 12,000 9,660 8,270 7,330 6,640 6,110 5,680 5,330 5,040 4,460 4,050 3,720 3,460
© 2007 National Fire Protection Association, Inc. and International Approval Services - U.S., Inc. All Rights Reserved.
GAS INSTRUCTIONS