Model 5100-02-IT Combustible Gas Sensor Module
Page: 38
|
|----▼ 4-20mA (Verifies 4mA or 20mA output and selects condition of output during calibration)
| |
| ▼ -------or--------------- E Calib
| | |
| | |- Out: 4mA
| | |
| | ▼ --or—E (To calibrate analog output 4mA, |▲ or ▼ to adjust level,
| | | then E t o accept)
| | |- Out: 20mA
| | ▼ --or--E (To calibrate analog output 20mA, |▲ or ▼ to adjust level,
| | | then E to accept)
| | |- In: 4mA
| | ▼ --or—E (To calibrate analog input 4mA, |▲ or ▼ to adjust level,
| | | then E to accept)
| | |- In: 20mA
| | ▼--or--E (To calibrate analog input 20mA, |▲ or ▼ to adjust level,
| | then E to accept)
| |
| ▼ -------or--------------- E CalibOut (Adjust 4-20mA output during Calibration)
| | |
| | |- Track: (▲ or ▼ (To adjust action/mA value during calibration
| | Track = mA value tracks Gas value
| | Hold = holds mA value existing prior to calibration
| | C1.50mA = 1.50 mA during calibration
| | C4.00 mA = 4.00 mA during calibration
| | User mA = |▲ or ▼ to adjust to desired mA value
| |
| ▼ -------or--------------- E Tbl Out (Adjust 4-20mA output during Trouble condition)
| | |
| | |- T2.50mA: (▲ or ▼ (To select 2.50mA or User mA, * = current value)
| | User mA = |▲ or ▼ to adjust to desired mA value
| |
| |
|----▼ RS-485 (Select RS-485 address and baud rate)
| |
| | - Address
| |
| ▼ | -------or--------------- E Addr:016 (Use (▲ or ▼ and E to select module address – 016 to 254)
| |
| |- Baud --------------- E *38400 (Use |▲ or ▼ and E to select baud rate, * = current selection)
MAINT MENU
MAINT::
|
E – V2.00aB (Software version installed on module)
|
E – CCC001 (Configuration number)