Model 5100-02-IT Combustible Gas Sensor Module
Page: 36
7.10 APPENDIX J: Menu Key for 5100-02-IT Gas Sensor Module
• Key M : MODE
• Key E : ENTER
• Key ▲ UP (+)
• Key ▼ DOWN (-)
MAIN MENU
Use the M key to access each of the 4 main sections of the menu.
M M M M M
| | | | |
|- ALMRSET: |- CALIB: |- SETUP: |- MAINT: |- EXIT?
ALARM RESET MENU
ALMRSET:
|
E– RESET (Resets current alarm)
CALIB MENU
CALIB:
|
E – CAL-0% (Calibrate Zero)
|
E – Ack (Acknowledges Zero)
|
*50%-SPAN (Last span gas used – initially set at 50%)
| |
| ▲ 25%-SPAN
| ▲ 50%-SPAN (Select Span gas value from below)
| ▲ 75%-SPAN
| ▲ Adj-SPAN (To select an alternate span gas value)
| |
| E 50%-SPAN
| |
| ▲ 51%-SPAN (Change span value to desired, once completed E starts calibration)
|
E C XX%LEL (Reading the value of the calibration gas being applied)
|
|- CAL-OK (if successful) or CAL-FAIL (if unsuccessful)