INSTALLATION
SPECIAL MOBILE HOME REQUIREMENTS
ÌWARNING! - DO NOT INSTALL IN A SLEEPING ROOM
ÌCAUTION! - THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL, AND CEILING/
ROOF MUST BE MAINTAINED.
In addition to the previously detailed installation requirements, mobile home installations must meet the following
requirements:
The stove must be permanently attached to the floor.
The stove must have a permanent outside air source (USSC Part No FAK1780 Fresh Air Kit is recommended).
The stove must be electrically grounded to the steel chassis of the mobile home with 8 GA copper wire using a ser-
rated or star washer to penetrate paint or protective coating to ensure grounding.
Vent must be 3 or 4-inch “PL” Vent and must extend a minimum or 36-inches above the roofline of the mobile
home and must be installed using a UL/ULC listed ceiling fire stop and rain cap.
When moving your mobile home, all exterior venting must be removed while the mobile home is being relocated.
After relocation, all venting must be reinstalled and securely fastened.
Check with your local building officials as other codes may apply.