-11-
INSTALLATION
OUTSIDE AIR SUPPLY
ÌThe use of outside air is mandatory for safe operation of this unit.
For all installations it is mandatory that this unit be connected to an outside air supply .
Metal pipe (solid or flexible) must be used for the outside air installation. PVC pipe is NOT approved and should
NEVER be used.
A wind shield over the termination of the outside air pipe or a 90-degree elbow or bend away from the prevailing
winds MUST be used when an outside air pipe is installed through the side of a building. The outside air termination
MUST be at least 1-foot away from the exhaust system termination.
The outside air pipe on your
Ashley Heritage Model 5700
stove is 1 7/8” OD. The outside air connecting pipe
must be at least 1 7/8” ID. The outside air connection used MUST NOT restrict the amount of air available to your
stove. The outside air connecting pipe must be as short and free of bends as possible, and it must fit over, not in-
side, the outside air connection to the stove (USSC Part No FAK1780 Fresh Air Kit is recommended).
FIGURE 8
EXHAUST/INLET LOCATIONS
NOTE: Dimensions from the floor to your
stoves inlet/exhaust pipes are approximate and
may vary depending on your installation.
FIGURE 9
TYPICAL OUTSIDE AIR TERMINATION
WIRE MESH
SCREEN
1 7/8” ID
WIND HOOD
2” MIN