Trane TSC060-120 Electric Heater User Manual


 
26
RT-PRC016-EN
Performance
Data
Table PD-13 — Belt Drive Evaporator Fan Performance -TSC102AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Mtr & Low Static Drive 1.50 Nom kW Standard Motor
&
Drive
4620 - - - - 646 0.50 689 0.58 734 0.67 781 0.77 826 0.88 865 0.98 898 1.07 928 1.16
5200 616 0.51 654 0.57 693 0.64 735 0.73 773 0.82 812 0.92 855 1.03 897 1.15 934 1.27 969 1.38
5780 675 0.68 711 0.75 743 0.82 781 0.91 819 1.01 853 1.11 886 1.21 925 1.34 964 1.47 1000 1.60
6350 735 0.89 770 0.97 799 1.04 830 1.12 865 1.23 899 1.34 930 1.45 960 1.56 994 1.68 1028 1.82
6930 796 1.14 828 1.23 857 1.31 883 1.39 913 1.48 945 1.60 977 1.72 1006 1.84 1034 1.96 1061 2.08
1.50 Nom kW Std Mtr 2.24 Nom kW Over-Sized
& High Static Drive Motor & High Static Drive
External Static Pressure (Pascals)
275 300 325 350 375 400 425 450 475 500
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Standard Motor & High Static Drive
4620 956 1.25 982 1.33 1008 1.42 1033 1.51 1056 1.60 1079 1.69 1102 1.78 1125 1.87 1146 1.95 1168 2.04
5200 999 1.49 1026 1.58 1052 1.68 1078 1.78 1101 1.88 1124 1.98 1146 2.08 1168 2.18 1188 2.27 1209 2.37
5780 1034 1.73 1067 1.86 1094 1.97 1120 2.08 1145 2.20 1168 2.31 1191 2.42 1213 2.53 1234 2.63 1254 2.74
6350 1063 1.96 1098 2.11 1129 2.26 1158 2.40 1185 2.53 1210 2.66 1234 2.78 1256 2.90 1278 3.03 1299 3.15
6930 1093 2.23 1125 2.38 1157 2.53 1188 2.70 1218 2.86 1245 3.01 1273 3.16 1297 3.31 - - - -
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Table PD-13a — Belt Drive Evaporator Fan Performance -TSC102AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Mtr & Low Static Drive 2 HP Standard Motor
&
Drive
2720 - - - - 646 0.67 689 0.78 734 0.90 781 1.04 826 1.18 865 1.31 898 1.44 928 1.56
3060 616 0.69 654 0.77 693 0.86 735 0.98 773 1.10 812 1.23 855 1.39 897 1.55 934 1.70 969 1.85
3400 675 0.92 711 1.01 743 1.10 781 1.22 819 1.36 853 1.49 886 1.62 925 1.79 964 1.97 1000 2.14
3740 735 1.20 770 1.30 799 1.40 830 1.51 865 1.65 899 1.79 930 1.94 960 2.09 994 2.26 1028 2.44
4080 796 1.53 828 1.65 857 1.76 883 1.86 913 1.99 945 2.15 977 2.30 1006 2.47 1034 2.63 1061 2.79
3 HP Over-Sized Mtr & Drive
2 HP Std Motor &
Hi Static Drive
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor
&
High Static Drive 3 HP Over-Sized Motor
&
Drive
2720 956 1.67 982 1.79 1008 1.91 1033 2.03 1056 2.14 1079 2.26 1102 2.38 1125 2.5 1146 2.62 1168 2.74
3060 999 1.99 1026 2.12 1052 2.26 1078 2.39 1101 2.52 1124 2.66 1146 2.79 1168 2.92 1188 3.05 1209 3.18
3400 1034 2.32 1067 2.49 1094 2.64 1120 2.79 1145 2.94 1168 3.09 1191 3.24 1213 3.39 1234 3.53 1254 3.68
3740 1063 2.63 1098 2.84 1129 3.03 1158 3.21 1185 3.39 1210 3.56 1234 3.73 1256 3.89 1278 4.06 1299 4.23
4080 1093 2.99 1125 3.19 1157 3.40 1188 3.62 1218 3.83 1245 4.03 1273 4.24 1297 4.44 - - - -
3 HP Over-Sized Motor
&
Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.