25
RT-PRC016-EN
Performance
Data
Table PD-12 — Belt Drive Evaporator Fan Performance -TSC102AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Standard Motor & Low Static Drive 1.50 Nom kW Standard Motor
&
Drive
4620 - - - - - - 613 0.45 655 0.54 695 0.62 733 0.71 769 0.81 802 0.90 833 1.00
5200 - - - - 611 0.48 650 0.55 688 0.64 725 0.73 761 0.83 796 0.93 828 1.03 861 1.13
5780 - - 612 0.51 651 0.59 689 0.68 724 0.76 759 0.86 792 0.96 825 1.07 856 1.18 887 1.28
6350 622 0.56 659 0.64 693 0.72 729 0.82 764 0.92 795 1.01 826 1.11 857 1.22 887 1.34 916 1.46
6930 671 0.71 706 0.80 738 0.89 770 0.98 804 1.09 834 1.19 864 1.30 892 1.40 920 1.52 948 1.64
1.50 Nom kW Standard
Motor & Hi Static Drive
←←
←←
←
External Static Pressure (Pascals)
275 300 325 350 375 400 425 450 475 500
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Mtr & Drive 1.50 Nom kW Std Mtr & Hi Static Dr
4620 863 1.11 892 1.21 920 1.33 946 1.44 973 1.55 999 1.67 1025 1.79 1050 1.90 1073 2.02 1098 2.14
5200 891 1.24 919 1.35 946 1.46 973 1.58 999 1.71 1024 1.83 1048 1.96 1072 2.09 1096 2.22 1119 2.34
5780 917 1.40 946 1.51 974 1.63 1001 1.75 1026 1.88 1051 2.01 1074 2.14 1099 2.27 1121 2.41 1143 2.55
6350 945 1.58 974 1.70 1001 1.82 1028 1.95 1054 2.08 1079 2.20 1103 2.34 1126 2.48 1148 2.62 1170 2.76
6930 976 1.78 1002 1.91 1029 2.04 1055 2.17 1081 2.30 1105 2.43 1130 2.58 1154 2.72 1176 2.85 1199 3.01
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Table PD-12a — Belt Drive Evaporator Fan Performance -TSC102AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor
&
Low Static Drive 2 HP Standard Motor
&
Drive
2720 - - - - - - 613 0.60 655 0.72 695 0.84 733 0.95 769 1.08 802 1.21 833 1.34
3060 - - - - 611 0.64 650 0.74 688 0.85 725 0.98 761 1.11 796 1.25 828 1.38 861 1.52
3400 - - 612 0.68 651 0.79 689 0.91 724 1.02 759 1.15 792 1.29 825 1.43 856 1.58 887 1.72
3740 622 0.76 659 0.86 693 0.97 729 1.10 764 1.23 795 1.35 826 1.49 857 1.64 887 1.79 916 1.96
4080 671 0.96 706 1.08 738 1.19 770 1.32 804 1.46 834 1.60 864 1.74 892 1.88 920 2.04 948 2.20
2 HP Standard Motor &
Hi Static Drive
←←
←←
←
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Mtr & Drive 2 HP Std Motor & Hi Static Drive
2720 863 1.48 892 1.63 920 1.78 946 1.93 973 2.08 999 2.24 1025 2.39 1050 2.55 1073 2.71 1098 2.88
3060 891 1.66 919 1.81 946 1.96 973 2.12 999 2.29 1024 2.46 1048 2.63 1072 2.80 1096 2.98 1119 3.14
3400 917 1.87 946 2.03 974 2.18 1001 2.34 1026 2.52 1051 2.69 1074 2.86 1099 3.05 1121 3.23 1143 3.41
3740 945 2.11 974 2.28 1001 2.44 1028 2.61 1054 2.78 1079 2.96 1103 3.14 1126 3.32 1148 3.51 1170 3.71
4080 976 2.38 1002 2.56 1029 2.73 1055 2.91 1081 3.09 1105 3.26 1130 3.45 1154 3.65 1176 3.83 1199 4.03
3 HP Over-Sized Motor & Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.