Trane TSC060-120 Electric Heater User Manual


 
20
RT-PRC016-EN
Performance
Data
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1/2 HP Standard Motor & Drive 1-1/2 HP Standard Motor & Hi Static Drive
1600 1206 1.12 1241 1.20 1275 1.28 1306 1.37 1338 1.46
1800 1256 1.32 1291 1.41 1326 1.50 1359 1.60 1390 1.69
2000 1309 1.56 1343 1.66 1376 1.76 - - - -
2200 - - - - - - - - - -
2400 - - - - - - - - - -
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
External Static Pressure (Pascals)
275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Drive
2720 1206 0.83 1241 0.89 1275 0.96 1306 1.02 1338 1.09
3060 1256 0.99 1291 1.05 1326 1.12 1359 1.19 1390 1.26
3400 1309 1.16 1343 1.24 1376 1.31 - - - -
3740 - - - - - - - - - -
4080 - - - - - - - - - -
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.12 Nom kW Standard Motor &
Hi Static Drive
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Table PD-7 - Belt Drive Evaporator Fan Performance- TSC060AD - Horizontal Configuration - (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Std Motor & Low Static Drive 1.12 Nom kW Standard Motor & Drive
2720 707 0.26 774 0.31 837 0.37 898 0.43 953 0.48 1001 0.54 1045 0.59 1087 0.65 1129 0.71 1168 0.77
3060 778 0.36 840 0.41 897 0.48 953 0.54 1008 0.60 1058 0.67 1102 0.73 1143 0.79 1181 0.85 1219 0.92
3400 850 0.48 908 0.54 961 0.60 1012 0.67 1062 0.74 1111 0.81 1157 0.88 1198 0.95 1237 1.02 1274 1.09
3740 923 0.63 978 0.69 1028 0.76 1075 0.83 1120 0.91 1166 0.99 1211 1.06 1254 1.14 1294 1.22 1330 1.29
4080 997 0.80 1049 0.87 1096 0.94 1140 1.02 1183 1.10 1223 1.18 1266 1.27 - - - - - -
1.12 Nom kW Standard Motor & Hi Static Drive
Table PD-7a - Belt Drive Evaporator Fan Performance- TSC060AD - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor &
Low Static Drive 1-1/2 HP Standard Motor & Drive
1600 707 0.35 774 0.42 837 0.50 898 0.57 953 0.65 1001 0.72 1045 0.80 1087 0.87 1129 0.95 1168 1.03
1800 778 0.48 840 0.56 897 0.64 953 0.72 1008 0.81 1058 0.89 1102 0.98 1143 1.06 1181 1.15 1219 1.23
2000 850 0.65 908 0.73 961 0.81 1012 0.90 1062 1.00 1111 1.09 1157 1.19 1198 1.28 1237 1.37 1274 1.47
2200 923 0.84 978 0.93 1028 1.02 1075 1.12 1120 1.22 1166 1.32 1211 1.43 1254 1.53 1294 1.63 1330 1.74
2400 997 1.07 1049 1.17 1096 1.27 1140 1.37 1183 1.48 1223 1.59 1266 1.70 - - - - - -
1-1/2 HP Standard Motor & Hi Static Drive