Trane TSC060-120 Electric Heater User Manual


 
24
RT-PRC016-EN
Performance
Data
Table PD-11 — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Motor & Low Static Drive 1.50 Nom kW Standard Motor
&
Drive
4080 - - 673 0.42 718 0.47 769 0.54 814 0.61 855 0.67 893 0.73 929 0.81 965 0.88 999 0.96
4590 702 0.51 738 0.56 773 0.62 817 0.68 862 0.76 904 0.85 941 0.92 975 0.98 1009 1.06 1041 1.14
5100 771 0.68 805 0.74 837 0.81 870 0.87 912 0.94 951 1.03 989 1.12 1025 1.21 1056 1.28 1088 1.36
5610 842 0.89 873 0.96 903 1.03 930 1.10 963 1.17 1000 1.25 1037 1.34 1073 1.45 1106 1.55 1136 1.63
6120 913 1.14 942 1.22 970 1.30 996 1.37 1021 1.45 1052 1.52 1086 1.61 1121 1.71 1153 1.82 1184 1.93
1.50 Nom kW Standard Motor
&
Drive 1.50 Nom kW Standard Motor & 2.24 Nom kW OS
Hi Static Drive Motor & Hi Static Drive
External Static Pressure (Pascals)
275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Standard Motor & Hi Static Drive
4080 1035 1.04 1070 1.12 1104 1.19 1137 1.27 1168 1.35
4590 1073 1.22 1104 1.31 1136 1.40 1167 1.48 1198 1.57
5100 1117 1.44 1146 1.53 1176 1.62 1205 1.72 1233 1.82
5610 1165 1.72 1194 1.80 1220 1.88 1248 1.98 1275 2.08
6120 1215 2.04 1242 2.13 1269 2.22 1295 2.31 1319 2.40
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Table PD-11a — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Motor & Low Static Drive 2 HP Standard Motor
&
Drive
2400 - - 673 0.56 718 0.63 769 0.72 814 0.82 855 0.90 893 0.98 929 1.08 965 1.18 999 1.29
2700 702 0.68 738 0.76 773 0.83 817 0.92 862 1.02 904 1.13 941 1.23 975 1.32 1009 1.42 1041 1.52
3000 771 0.91 805 1.00 837 1.08 870 1.17 912 1.26 951 1.38 989 1.51 1025 1.62 1056 1.72 1088 1.82
3300 842 1.19 873 1.29 903 1.38 930 1.47 963 1.57 1000 1.68 1037 1.80 1073 1.94 1106 2.08 1136 2.19
3600 913 1.53 942 1.63 970 1.74 996 1.84 1021 1.94 1052 2.04 1086 2.16 1121 2.29 1153 2.44 1184 2.59
2 HP Standard Motor
&
Drive 2 HP Std Motor & Hi Static Drive
3 HP Over-Sized Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor
&
Hi Static Drive
2400 1035 1.39 1070 1.50 1104 1.60 1137 1.70 1168 1.81
2700 1073 1.64 1104 1.76 1136 1.87 1167 1.99 1198 2.11
3000 1117 1.93 1146 2.05 1176 2.17 1205 2.31 1233 2.44
3300 1165 2.30 1194 2.41 1220 2.52 1248 2.66 1275 2.79
3600 1215 2.73 1242 2.86 1269 2.98 1295 3.10 1319 3.22
3 HP Over-Sized Motor
&
High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.