Trane PKGP-PRC001-EN Heat Pump User Manual


 
PKGP-PRC001-EN
31
Electrical
Data
Table ED-4 — Electrical Characteristics — Evaporator Fan Motors — 60 Cycle
Standard Evaporator Fan Motor Oversized Evaporator Fan Motor
Unit
Amps Amps
Tons Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA
WC*150B3 1 208-230 3 3.00 10.6 81.0 1 208-230 3 5.00 16.7 109.8
12½ WC
*150B4 1 460 3 3.00 4.8 40.5 1 460 3 5.00 7.6 54.9
WC
*150BW 1 575 3 3.00 3.9 31.0 1 575 3 5.00 6.1 41.6
WC*180B3 1 208-230 3 3.00 10.6 81.0 1 208-230 3 5.00 16.7 109.8
15 WC
*180B4 1 460 3 3.00 4.8 40.5 1 460 3 5.00 7.6 54.9
WC
*180BW 1 575 3 3.00 3.9 31.0 1 575 3 5.00 6.1 41.6
WC*240B3 1 208-230 3 5.00 16.7 109.8 1 208-230 3 7.50 17.6 120.4
20 WC
*240B4 1 460 3 5.00 7.6 54.9 1 460 3 7.50 8.6 74.0
WC
*240BW 1 575 3 5.00 6.1 41.6 1 575 3 7.50 7.0 60.0
*Indicates both downflow and horizontal units.