Trane PKGP-PRC001-EN Heat Pump User Manual


 
12
PKGP-PRC001-EN
(12½ Ton)
General
Data
*Indicates both downflow and horizontal units.
Table GD-1 — General Data
12½ Ton Downflow and Horizontal Units
WCD150B3, B4, BW WCH150B3, B4, BW
Cooling Performance
1
Gross Cooling Capacity 152,00 152,000
EER
2
9.5 9.5
Nominal CFM / ARI Rated CFM 4,400 / 4,400 4,400 / 4,400
ARI Net Cooling Capacity 144,000 144,000
Integrated Part Load Value
3
9.9 9.9
System Power KW 15.16 15.16
Heating Performance
1
High Temp. Btuh Rating 135,000 132,000
System Power KW/COP 12.76/3.10 12.48/3.10
Low Temp. Btuh Rating 78,000 72,000
System Power KW/COP 10.88/2.1 10.55/2.0
HSPF (Btu/Watts-hr)
Compressor
No./Type 2/Scroll 2/Scroll
ARI Sound Rating (BELS)
4
9.2 9.2
Outdoor Coil — Type Hi-Performance Hi-Performance
Tube Size (in.) OD .375 .375
Face Area (sq ft) 23.96 23.96
Rows/FPI 2/16 2/16
Refrigerant Control Expansion Valve Expansion Valve
Indoor Coil — Type Hi-Performance Hi-Performance
Tube Size (in.) .375 .375
Face Area (sq ft) 15.83 17.50
Rows/FPI 2/15 2/15
Refrigerant Control Capillary Tube Capillary Tube
Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT
Outdoor Fan — Type Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26
Drive Type/No. Speeds Direct/1 Direct/1
CFM 10,800 10,800
No. Motors/HP 2/.50 2/.50
Motor RPM 1,110 1,110
Indoor Fan — Type FC Centrifugal FC Centrifugal
No. Used 1 1
Diameter x Width (in.) 15 x 15 15 x 15
Drive Type/No. Speeds Belt/1 Belt/1
No. Motors 1 1
Motor HP (Standard/Oversized) 3.0/5.0 3.0/5.0
Motor RPM (Standard/Oversized) 1,740/3,450 1,740/3,450
Motor Frame Size (Standard/Oversized) 145T/145T 145T/145T
Filters — Type Furnished
6
Throwaway Throwaway
(No.) Size Recommended (in.) (2) 20 x 20 x 2 (2) 20 x 20 x 2
(4) 20 x 25 x 2 (4) 20 x 25 x 2
Refrigerant Charge (Lbs of R-22)
5
11.1/11.4 Circuit 11.5/11.8 Circuit
Notes:
1. Cooling Performance and Heating Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat.
ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ASHRAE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 340. Units are rated at 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Optional 2 inch pleated filter also available.