Trane PKGP-PRC001-EN Heat Pump User Manual


 
22
PKGP-PRC001-EN
Performance
Data (12½ Ton)
Table PD-14 — 12½ Ton Downflow Three Phase Heating Capacities (Net) WCD150B3, B4, BW at 5000 CFM
Outdoor
Integrated Heating Capacity (MBh/1000) Total Power in Kilowatts At
Temp.
At Indicated Indoor Dry Bulb Temp. Indicated Indoor Dry Bulb Temp.
F. 60 70 75 80 60 70 75 80
-8 51.9 50.3 49.6 49 9.56 10.37 10.83 11.32
-3 56.8 55.3 54.6 54 9.61 10.45 10.92 11.42
2 62.1 60.7 60 59.4 9.74 10.55 11.03 11.53
7 67.9 66.4 65.7 65.1 9.85 10.72 11.2 11.71
12 74.1 72.6 71.9 71.1 9.98 10.87 11.36 11.88
17 80.7 79.1 78.3 77.6 10.13 11.03 11.53 12.06
22 87.8 86 85.1 84.3 10.3 11.22 11.72 12.26
27 95.3 93.3 92.3 91.4 10.48 11.41 11.92 12.48
32 103.2 101 99.9 98.9 10.68 11.62 12.14 12.7
37 111.1 108.6 107.4 106.3 10.89 11.84 12.37 12.94
42 119.2 116.4 115.1 113.9 11.11 12.07 12.61 13.18
47 138.6 135.3 133.8 132.3 11.93 12.96 13.53 14.14
52 148.1 144.5 142.9 141.2 12.2 13.25 13.83 14.43
57 155.6 151.4 149.4 147.4 12.46 13.49 14.06 14.67
62 168.8 164.2 161.9 159.7 12.8 13.86 14.43 15.04
67 179.3 174.3 171.8 169.4 13.17 14.24 14.82 15.44
72 189.9 184.5 181.8 179.1 13.55 14.64 15.23 15.85
For other airflow conditions, see heating capacity correction factor (Table PD-19).
Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and .35 inch ESP. To obtain net heating at other conditions,
subtract fan heat at this condition and add fan heat at new condition.
Heating capacities and powers are integrated to include the effects of defrost in the frost region.
All heating capacities and power (kW) are at 70% OD relative humidity.
Table PD-15— 12½ Ton Horizontal Three Phase Heating Capacities (Net) WCH150B3, B4, BW at 5000 CFM
Outdoor
Integrated Heating Capacity (MBh/1000) Total Power in Kilowatts At
Temp.
At Indicated Indoor Dry Bulb Temp. Indicated Indoor Dry Bulb Temp.
F. 60 70 75 80 60 70 75 80
-8 48.2 46.6 46 45.4 9.18 9.96 10.4 10.87
-3 52.7 51.3 50.6 50 9.23 10.03 10.48 10.96
2 57.7 56.3 55.7 55.1 9.35 10.13 10.58 11.07
7 63.1 61.7 61.1 60.4 9.46 10.29 10.75 11.24
12 68.9 67.5 66.8 66.1 9.58 10.43 10.9 11.4
17 75.2 73.6 72.9 72.1 9.73 10.59 11.07 11.58
22 81.8 80.1 79.3 78.4 9.88 10.77 11.25 11.77
27 88.9 87 86 85.1 10.06 10.96 11.45 11.98
32 96.3 94.2 93.1 92.1 10.25 11.16 11.66 12.2
37 103.7 101.4 100.2 99.1 10.45 11.37 11.88 12.42
42 111.3 108.7 107.5 106.3 10.67 11.6 12.11 12.66
47 137.3 133.9 132.4 130.9 11.53 12.52 13.07 13.66
52 146.8 143.1 141.4 139.8 11.8 12.8 13.36 13.96
57 154.4 150.1 148.1 146.1 12.04 13.04 13.6 14.19
62 167.7 162.9 160.7 158.4 12.37 13.39 13.95 14.55
67 178.1 173.1 170.6 168.2 12.72 13.76 14.33 14.93
72 188.8 183.4 180.7 178 13.1 14.15 14.73 15.33
For other airflow conditions, see heating capacity correction factor (Table PD-19).
Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and .40 inch ESP. To obtain net heating at
other conditions, subtract fan heat at this condition and add fan heat at new condition.
Heating capacities and powers are integrated to include the effects of defrost in the frost region.
All heating capacities and power (kW) are at 70% OD relative humidity.