Trane PKGP-PRC001-EN Heat Pump User Manual


 
PKGP-PRC001-EN
27
Table ED-2 — Electrical Characteristics — Power Exhaust Accessory
Accessory
Operating
Amps
Tons Voltage Phase HP RPM FLA LRA
208-230 1 3/4 1040 6.6 13.5
460 1 3/4 1040 3.2 8.4
575 1 3/4 1040 2.1 5.2
Table ED-1 — Unit Wiring
Standard Indoor Fan Motor Oversize Indoor Fan Motor
Unit Minimum Maximum Fuse Size Minimum Maximum Fuse Size
Unit Operating Circuit or Maximum Circuit or Maximum
Tons Model No. Voltage Range Ampacity Circuit Breaker
1
Ampacity Circuit Breaker
1
WC*150B3 187-253 66.0 80 72.0 80
12½ WC
*150B4 414-506 31.0 40 34.0 40
WC
*150BW 517-633 25.0 30 28.0 35
WC*180B3 187-253 76.0 90 82.0 100
15 WC
*180B4 414-506 39.0 45 42.0 50
WC
*180BW 517-633 31.0 35 33.0 40
WC*240B3 187-253 96.0 125 103.0 125
20 WC
*240B4 414-506 49.0 60 53.0 60
WC
*240BW 517-633 38.0 45 41.0 50
Note:
1. HACR type circuit breaker per NEC.
Electrical
Data
*Indicates both downflow and horizontal units.
12½, 15, 20