Toshiba RAV-SM2802DT-E Air Conditioner User Manual


 
– 33 –
Main remote controller (RBC-AMT32E)
How to read check monitor display
<7-segment display>
n Confirmation of error log
When an error occurred on the air conditioner,
the error log can be confirmed with the following
procedure. (The error history is stored in
memory up to 4 errors.)
The log can be confirmed from both operating
status and stop status.
Procedure 1
When pushing
SET
and
TEST
buttons at the same time
for 4 seconds or more, the following display appears.
If is displayed, the mode enters in the error log
mode.
•[01: Order of error log] is displayed in CODE No.
[Error code] is displayed in CHECK.
[Indoor unit address in which an error occurred] is
displayed in Unit No..
Procedure 2
Every pushing of
TEMP.
button used to set
temperature, the error log stored in memory is
displayed in order.
The numbers in CODE No. indicate CODE No.
[01] (latest) [04] (oldest).
REQUIREMENT
Do not push
CL
button because all the error log of
the indoor unit will be deleted.
Procedure 3
After confirmation, push
TEST
button to return to the
usual display.
Error code Indoor UNIT No. in
which an error occurred
3
2
1
n Confirmation and check
When an error occurred in the air conditioner, an
error code and indoor UNIT No. appear on the
display part of the remote controller.
The error code is only displayed during the
operation.
If the display disappears, operate the air
conditioner according to the following
“Confirmation of error log” for confirmation.