Toshiba RAV-SM1603DT-A Air Conditioner User Manual


 
– 78 –
[P19 error]
Check method of outdoor P.C. board operation (Self-hold valve type : SP110, SP140)
1) Set SW804 of Dip switch as the following figure and then push SW801 for approx. 1 second to check
exchange operation to cooling cycle/heating cycle.
Power is turned on for approx. 10 seconds.
When checking again, check operation 1 minute or more after the first check because exothermic of part
(Coil, resistance R700) is large. (There is no problem when coil is not connected.)
2) After check, turn off all the Dip switch SW804.
Note) Check by tester
Analog tester : Good if over DC200V
Digital tester : Good if Max. value is over DC200V though the varied value may be displayed.
Check outdoor P.C. board.
Defect replace
Replace coil of 4-way valve.
Temperature sensor check
TE sensor CN601
TS sensor CN600
Indoor TC sensor
Defect Correct and repair
Is the coil resistance value of
4-way valve between 1.3 and 1.6k?
Check operation of outdoor P.C. board.
(See below.)
Is operation of 4-way valve normal?
(Check pipe temp., etc. in cooling/heating operation.)
Check 4-way valve.
Defect Replace
YES
YES
NO
NO
Error
OK
ON
1234
ON
1234
SW804 SW801 CN701
Push
DC200V or more
1
4
SW804 SW801 CN701
Push
DC200V or more
1
4
Exchange to cooling cycle Exchange to heating cycle