Toshiba RAV-SM1603DT-A Air Conditioner User Manual


 
– 33 –
4-3. Fan Characteristics
Current value as a criterion, adjust the air volume value to become within the range of the chart below.
REQUIREMENT
Install the volume damper in the air outlet, and adjust the airflow to become within the range of the chart above.
n Wire connection change of fan motor
Wiring connection of the fan motor is connected that external static pressure makes to 200P during factory setting.
In cases where external static pressure is required to change by the duct resistor, change the wiring connection.
The fan motor connector is connected to the 9P white color connector during factory setting.
When the fan motor is set to high static pressure, connect to the 9P red color connector such as arrow mark.
In addition, 9P red color connector is bundled along with wirings into the electric parts box.
<RAV-SM1403DT-A> <RAV-SM1603DT-A>
Fan-tap
Hi
Med
Low
(unit)
m³/h
l/s
CMM
m³/h
l/s
CMM
m³/h
l/s
CMM
Static pressure (Pa)
30 40 50 100 200 225 250
3,480 3,300 2,500 2,330 2,100
966 916 694 647 583
58.0 55.0 41.6 38.8 35.0
2,700 2,670 2,500 2,100 1,900
750 742 694 583 527
45.0 44.5 41.6 35.0 31.6
2,300 2,270 2,250 2,100 1,600
638 631 625 583 513
38.3 37.8 37.5 35.0 30.8
Fan-tap
Hi
Med
Low
(unit)
m³/h
l/s
CMM
m³/h
l/s
CMM
m³/h
l/s
CMM
Static pressure (Pa)
30 40 50 100 200 225 250
3,740 3,500 2,800 2,600 2,300
1,038 972 777 722 638
62.3 58.3 46.6 43.3 38.3
3,000 2,970 2,790 2,260 2,000
833 825 775 627 555
50.0 49.5 46.5 37.6 33.3
2,600 2,580 2,550 2,380 1,850
722 717 708 66 513
43.3 43.0 42.5 39.6 30.8
1,500
300 300
250 250
200 200
150 150
100 100
50 50
0 0
6 6
5 5
4 4
3 3
2 2
1 1
0 0
2,000 2,500 3,000 3,500 4,000 1,500 2,000 2,500 3,000 3,500 4,000
Static pressure (Pa)
Motor current (A)
Static pressure (Pa)
Motor current (A)
Air volume (m³/h) Air volume (m³/h)
Normal
condition
(ex factory)
Normal
condition
(ex factory)
High static pressure
Low Med.
Hi
Low
Med.
Hi
Low Med.
Hi
Low
Med.
Hi
High static pressure
White color
connector
In case of normal condition
(Factory setting)
Red
White
White
Brown
Brown
RC
Yelow
Blue
Orange
Yelow
Yelow
Blue
Blue
Black
Black
Orange
Black
Gray
1 3 4 5 6 9
1 3 4 5 6 7 9
FM
White color
connector
In case of high static pressure
Closed end
connector
Red color connector
Red
White
White GrayGray
RedRed Red
Yelow
Blue
Orange
Black
Gray
1 3 4 5 7 9
1 3 4 5 6 7 9
FM
2
6
4
5
3
43F1
6
4
5
3
43F2
6
4
5
3
43F3