Toshiba RAV-SM1400AT-E Air Conditioner User Manual


 
41
4. Outdoor fan control (Object: SM800, SM1100, SM1400)
Allocautions of fan tap revolutions [rpm]
TO
MIN
MAX
TO < 5°C5 TO <10°C 10 TO < 15°C 15 TO < 20°C 20 TO < 25°C25°C TO TO error
W1 W2 W3 W4 W5 WA W1
W6 W8 WA WC WE WE WE
2) Heating fan control
This control function lowers fan tap according to
TE sensor value when outdoor temperature is
high.
When a status TE > 20°C is detected continu-
ously for 5 minutes, the operation may stop. This
status does not output an error code and is
assumed as usual status of thermo-OFF. The fan
restarts after approx. 2 minutes 30 seconds and
this intermittent operation is not a trouble.
If the status in item
is frequently found, it is
considered that the filter of suction part of the
indoor unit is dirty. Clean the filter and restart the
operation.
This control function does not work for 30 min-
utes after activation, 1 minute after defrosting,
and during defrost operation.
Control for fan tap by outdoor temperature in normal operation
1) Cooling fan control
The outdoor fan is controlled by TE sensor.
(Cooling: Temperature conditions after medium
term)
The cooling fan is controlled by every 1 tap of DC
fan control (14 taps).
At the activation time, although the maximum fan
tap in the following table are fixed for 60 seconds,
after then the fan may not rotate with high speed
for several minutes because the fan is controlled
by TE sensor value. It is not an abnormal status.
When the discharge temperature sensor is
abnormal or the sensor comes off the holder, the
fan does not rotate with high speed, but a protec-
tive device works.
When the outdoor fan does not rotate with high
speed, judge a fan error by comparing the control
data in the following table with TO and TE values.
MAX.
+30 rpm / 20 sec.
Hold zone
30 rpm / 20 sec.
MIN.
46
37
34
20
TE [˚C]
60 rpm / 20 sec. STOP timer count
60 rpm / 20 sec.
30 rpm / 20 sec.
Hold zone
+30 rpm / 20 sec.
24
21
17
15
TE [˚C]
SM800
SM1100
SM1400
Upper fan
Lower fan
Upper fan
Lower fan
W1 W2 W3 W4 W5 W6 W7 W8 W9 WA WB WC WD WE
250 270 290 310 340 370 400 440 480 520 560 610 700 780
250 280 300 320 340 380 420 470 520 570 630 690 740 800
OFF OFF 270 290 400 480 520 560 600 660 720 780 860 940
250 270 270 300 350 410 470 530 590 670 750 810 840 860
OFF OFF 240 270 330 390 450 510 570 650 730 790 820 840