12. SETUP AT LOCAL SITE AND OTHERS
12-1. Indoor Unit
12-1-1. Test Run Setup on Remote Controller
<Wired remote controller>
1. When pushing button on the remote controller for 4 seconds or more, TEST is displayed on LC display.
Then push button.
•“TEST is displayed on LC display during operation of Test Run.
During Test Run, temperature cannot be adjusted but air volume can be selected.
In heating and cooling operation, a command to fix the Test Run frequency is output.
Detection of error is performed as usual. However, do not use this function except case of Test Run be-
cause it applies load on the unit.
2. Use either heating or cooling operation mode for [TEST].
NOTE : The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after
operation has stopped.
3. After a Test Run has finished, push button again and check that [TEST] on LC display has gone off.
(To prevent a continuous test run operation, 60-minutes timer release function is provided to this remote
controller.)
12-1-2. Setup to Select Function
<Procedure> Use this function while the indoor unit stops.
1
Push
SET
, , and buttons concurrently for 4 seconds or more.
The unit No. displayed at the first time indicates the indoor unit address of the master unit in the group control.
In this time, fan and flap of the selected indoor unit operate.
2
Every pushing button, the indoor unit numbers in the group control are displayed successively.
In this time, fan and flap of the selected indoor unit only operate.
3 Using the set temperature / buttons, set the item code (DN).
4
Using the timer time / buttons, select the setup data.
5
Push
SET
button. (OK if display goes on.)
To change the selected indoor unit, proceed to
2
.
To change the item to be set, proceed to
3
.
6
Pushing button returns the status to usual stop status.
UNIT
SET
CL
UNIT No.
SET DATA
R.C. No.
4
6
1
3
5
1 2 3 4 5 6
2
END
<Operation procedure>