Toshiba RAV-SM1101BT-E Air Conditioner User Manual


 
3
1-2. Outdoor Unit
Model name
Appearance
Power supply
Type
Compressor Motor (kW)
Pole
Refrigerant charged (kg)
Refrigerant control
Standard length
Max. total length (m)
Pipe Over 20m
Height difference
Outdoor lower (m)
Outdoor higher (m)
Outer
Height (mm)
Width (mm)
dimension
Depth (mm)
Total weight (kg)
Heat exchanger
Fan
Fan unit Standard air flow High (m³/h)
Motor (W)
Connecting
Gas side (mm)
pipe
Liquid side (mm)
Protection device
Sound level High (Mid./Low)
(dB•A)
(Note 2) (Cooling/Heating)
RAV-SM560AT-E RAV-SM800AT-E
Silky shade (Muncel 1Y8.5/0.5)
1 phase 230V (220 – 240V) 50Hz
(Power exclusive to outdoor is required.)
Hermetic compressor
1.1 1.6
8 poles
R410A 0.9 R410A 1.5
Pulse motor valve
20 (without additional charge)
30 50
Add 20g/m (Max. 200g) Add 40g/m (Max. 1200g)
30
50
595 795
780 780
270 270
35 55
Finned tube
Propeller fan
2400 3400
43 63
Ø12.7 (1/2”) Ø15.9 (5/8”)
Ø6.4 (1/4”) Ø9.5 (3/8”)
Discharge temp. sensor
Over-current sensor
Compressor thermo.
46/48 45/50
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB