Coupling size of brazed pipe
(Unit: mm)
Selection of pipe size
◆Capacity code of indoor and outdoor units
Selection of pipe material
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor units differs
based on the height difference between the indoor units.
• When the height difference between the indoor units is 15m or less: Up to 135% of the capacity code (Equivalent
to HP) of the outdoor unit (Equivalent to HP) of the outdoor unit
• When the height difference between the indoor units is over 15m: Up to 105% of the capacity code
Connected section
External size Internal size
Standard outer dia.
of connected
copper pipe
Connected section
Min. thickness
of coupling
External size Internal size
Min. depth of
insertion
Oval value
Standard outer dia.
(Allowable difference)
CFKG
6.35 6.35 (±0.03) 6.45 ( ) 7 6 0.06 or less 0.50
9.52 9.52 (±0.03) 9.62 ( ) 8 7 0.08 or less 0.60
12.70 12.70 (±0.03) 12.81 ( ) 9 8 0.10 or less 0.70
15.88 15.88 (±0.03) 16.00 ( ) 9 8 0.13 or less 0.80
19.05 19.05 (±0.03) 19.19 ( ) 11 10 0.15 or less 0.80
22.22 22.22 (±0.03) 22.36 ( ) 11 10 0.16 or less 0.82
28.58 28.58 (±0.04) 28.75 ( ) 13 12 0.20 or less 1.00
34.92 34.90 (±0.04) 35.11 ( ) 14 13 0.25 or less 1.20
38.10 38.10 (±0.05) 38.31 ( ) 15 14 0.27 or less 1.26
41.28 41.28 (±0.05) 41.50 ( ) 15 14 0.28 or less 1.35
K
ØC
G
ØF
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.03
-0.03
+0.03
-0.03
+0.06
-0.02
+0.04
-0.04
+0.08
-0.02
+0.08
-0.02
Table 1
Table 2
* For combination of the outdoor units, refer to “Combination of outdoor units”.
Indoor unit
capacity rank
Capacity code
Equivalent to HP
Equivalent to
capacity
007 0.8 2.2
009 1 2.8
012 1.25 3.6
015 1.7 4.5
018 2 5.6
024 2.5 7.1
027 3 8
030 3.2 9
036 4 11.2
048 5 14
056 6 16
072 8 22.4
096 10 28
Outdoor unit
model name
(Standard model)
Capacity code
No. of
indoor
units
Outdoor unit
model name
(High Efficiency
model)
Capacity code
No. of
indoor
units
Equivalent to
HP
Equivalent to
capacity
Equivalent to
HP
Equivalent to
capacity
MMY-MAP0804∗ 822.413— — ——
MMY-MAP1004∗ 10 28 16 — — — —
MMY-MAP1204∗ 12 33.5 20 — — — —
MMY-MAP1404∗ 14 40 23 — — — —
MMY-MAP1604∗ 16 45 27 MMY-AP1624∗ 16 45 27
MMY-AP1814∗ 18 50.4 30 — — — —
MMY-AP2014∗ 20 56 33 — — — —
MMY-AP2214∗ 22 61.5 37 — — — —
MMY-AP2414∗ 24 68 40 MMY-AP2424∗ 24 68 40
MMY-AP2614∗ 26 73 43 MMY-AP2624∗ 26 73 43
MMY-AP2814∗ 28 78.5 47 MMY-AP2824∗ 28 78.5 47
MMY-AP3014∗ 30 85 48 MMY-AP3024∗ 30 85 48
MMY-AP3214∗ 32 90 48 MMY-AP3224∗ 32 90 48
MMY-AP3414∗ 34 96 48 MMY-AP3424∗ 34 96 48
MMY-AP3614∗ 36 101 48 MMY-AP3624∗ 36 101 48
MMY-AP3814∗ 38 106.5 48 MMY-AP3824∗ 38 106.5 48
MMY-AP4014∗ 40 112 48 MMY-AP4024∗ 40 112 48
MMY-AP4214∗ 42 118 48 MMY-AP4224∗ 42 118 48
MMY-AP4414∗ 44 123 48 MMY-AP4424∗ 44 123 48
MMY-AP4614∗ 46 130 48 MMY-AP4624∗ 46 130 48
MMY-AP4814∗ 48 135 48 MMY-AP4824∗ 48 135 48
21-EN 22-EN