SPX Cooling Technologies 1000 Humidifier User Manual


 
Marley
/
Sigma 1000 Cooling Tower
/
Engineering Data : Support
6
W
OVERALL WIDTH OF BASIN
C
BAYS @ 4'-0 =
L
EACH ADDITIONAL CELL =
L
7
1/2
" 7
1/2
"
AIR INLET FACE
11
1/2
"
A
C
L
C
L
OVERALL LENGTH OF BASIN
C
L
C
L
B
A
B
C
L
TOWER
C
L
C
L
AIR INLET FACE
ENDWALL FACE
ENDWALL FACE
OVERFLOW
SUMP
ADDITIONAL SUMP
WHEN REQUIRED
11
1/2
"
7/8" ANCHOR
BOLT HOLES
7/8" ANCHOR
BOLT HOLES
7/8" ANCHOR
BOLT HOLES
C
L
7/8" ANCHOR
BOLT HOLES
7/8" ANCHOR
BOLT HOLES
PLAN
NotE
1 Use this bulletin for preliminary layouts only. All
dimensions show anchor bolt locations. Obtain current
drawings from your Marley sales representative before
designing supports.
2 Other contractors or purchaser must design and erect
supporting steel.
3 If steel beams are used, they must include
7
8" dia. holes to
accept anchor bolts provided. If concrete beams or pilasters
are used,
3
4" dia. anchor bolts embedded in the concrete must
be provided by others.
4 Maintain no less than 2'-0" of clear space at endwall faces for
construction purposes. Air inlet faces must have unobstructed
air supply. Consult your Marley sales representative if nearby
obstructions may interfere.
5 Operating weight is wet weight of tower and wood basin,
including 6" of water in the collection basin. This is the
recommended operating water level for all models.
Tower
Model
Dimensions Operating Weight lb
W A B C L Single Cell Each Cell Add
1011 22'-1" 4'-10" 5'-3" 2 8'-0" 23620 20500
1021 22'-1" 4'-10" 5'-3" 3 12'-0" 32140 28980
1031 24'-5" 4'-10" 6'-5" 3 12'-0" 34440 31020
1041 26'-8" 4'-10" 7'-6
1
2" 4 16'-0" 47620 44000