8
/ Steel Basin Support /
1. Use this bulletin for preliminary layouts only. All dimensions show
column locations, not anchor bolt locations. Obtain current
drawings from your Marley sales representative before designing
supports.
2. Other contractors or purchaser must design and erect support-
ing steel.
3. If steel beams are used, they must include ⁷⁄₈″ dia. holes to
accept anchor bolts provided by Marley. If concrete beams or
pilasters are used, ³⁄₄″ dia. anchor bolts imbedded in the con-
crete must be provided by others.
4. Maintain no less than 2′-0″ of clear space at cased faces for
construction purposes. Air inlet faces must have unobstructed
air supply. Consult your Marley sales representative if nearby
obstructions may interfere.
5. Operating weight is wet weight of tower and wood basin,
including 6″ of water in the cold water basin. This is the recom-
mended operating water level for all models.
6. For collection basin accessories information request Marley
drawing 90-3231 from your Marley sales representative.
Note: Two beams shown phantom are required on Models 1651 and 1661 only. All
dimensions are to centers of tower columns—not centers of anchor bolts or beams.
REWO4
LEDO-
SNOISNEMI$
THGIE7GNITAREP/
BL
7 !"#$%,
LLE#ELGNI3 DD!LLE#HCA%
a q a 6 q a q a q
a q a 6 q a q a q
a q a 6 q a q a q
a q a 6 q a q a q
a q a 6 q a 6( q a 65 q a q
a q a 6 q a O65 q a O65 q a q
FACE “D”
AIR INLET FACE
FACE “A” CASED FACE
SUMP
ADDITIONAL SUMP
WHEN REQUIRED
ADDITIONAL OVERFLOW
WHEN REQUIRED
OVERFLOW
C
B AA B
DD C
76q76q
C
L
C
L
COL.COL.
W OVERALL WIDTH OF BASIN
FACE “C” CASED FACE
756Oq 756Oq
C
L
C
L
COL.
COL.
C
L
COL.
OUT OF
BASIN
OUT OF
BASIN
E BAYS @ 4a-0q= L EACH ADDITIONAL CELL= L
FACE “B”
AIR INLET FACE