Sears EF16J2200A2 Furnace User Manual


 
I Blower Coils Installation Instructions
Sequence Of Operation
Mode | Thermostat to Con- Control Function
J
trol Board 24 volt
Constant Blower
Fan Switch ON)
G
Thermostat calls for
Heat
Constant Blower
Fan Switch ON)
Cooling Only Unit
(Thermostat calls for
Cooling)
Cooling Only Unit
(Thermostat calls for
Heat)
Heat Pump
(Thermostat calls for
Cooling)
G&W1 &W2
G
Y&G
G&W1 &W2
Y&G&O
Heat Pump Y & G
(Thermostat calls for
Heat)
Heat Pump cannot Y & G & Wl & W2
maintain proper temp.
Control
State
Electric Heat Only
On Fan On.
Off
On
Off
Fan Off.
Fan On, 1st Stage Of Heat On, then 2nd Stage Of Heat On.
2nd thenlst Stage Of Heat Off. 6 sec delay, then Fan Off.
Electric Heat Tempera-
ture satifised
Heat Pump
(Goes into Defrost
Mode)
Cooling Only
On
Off
On
Off
On
Off
Heat Pump
Room temp. satifised)
Heat Pump
(Emergency Heat)
Y&G&O&WI&W2
Y&G
G&W1 &W2
Unit With Electric Heat
Fan On.
Fan Off.
Compressor On, Fan On.
Compressor Off, 60 Second Delay - Then Fan Off.
Fan On, 1st Stage Of Heat On, then 2nd Stage Of Heat On.
2rid thenlst Stage Of Heat Off. 6 sec delay, then Fan Off.
Heat Pump With Electric Heat
On
Off
On
On
Off
On
Off
Off
On
Off
Compressor On, Reversing Valve Energized, Fan On.
Compressor Off, 60 Second Delay And Then Fan Off.
Compressor On, Fan On
1st Stage Of Heat On, then 2nd Stage Of Heat On
2rid then 1st Stage Of Heat Off
Reversing valve switches unit to cooling, 1st Stage Of Heat
On, then 2nd Stage Of Heat On
Reversing valve switches back to heating, 2rid then 1st Stage
Of Heat Off
Compressor Off, 60 Second Delay And Then Fan Off.
Fan On, 1st Stage Of Heat On, then 2nd Stage Of Heat On.
2rid then 1st Stage Of Heat Off. 6 sec delay, then Fan Off.
NOTE: Electric Heat Elements are controlled by relays with a delay sequence from the logic board to provide sequencing between elements.
LimitOperation
The temperature limit responds to over-temperature conditions in the air duct. Ifthetemperaturelimittrips, theelectricheaterrelayswill
be de-energized and the fan relay will be energized. Once the limit resets, the control will resume normal operation. Ifthe limit trips four
times during a single call for heat, the control will go into a 1 hour soft lockout. During the soft lockout, the fan relay will respond to
thermostat inputs but the heater relays are disabled. If the control detects a limit trip during the soft lockout, the control will go into ahard
lockout. Once ina hard lockout, the fan relay is locked on and the heater relays are disabled. Turning the power tothe unit off and then on
will clear this state.
442 01 2204 01 9L_