Sea-Fire FM200 Fire Extinguisher User Manual


 
WARNING
CONCENTRATED AGENT AND BY-PRODUCT OF APPLICATION TO FIRE ARE TOXIC.
AVOID BREATHING OF FUMES OR PROLONGED EXPOSURE. ACCIDENTAL DIS-
CHARGE MAY OCCUR DURING HANDLING OR INSTALLATION OF THIS DEVICE, READ
AND COMPLY WITH INSTRUCTIONS, WARNINGS, AND LIMITATIONS CONTAINED IN
THIS MANUAL. DO NOT LIFT, CARRY, OR HANDLE BY VALVE. DO NOT DROP. KEEP
AWAY FROM HEAT. KEEP AWAY FROM CHILDREN.
APPLICATION
FM-200
®
(CF3CHFCF3), the extinguishing agent, used in all Sea-Fire “FT’’ series fire extin-
guishers, is a suitable EPA accepted alternate replacement for Halon. FM-200
®
is electrically
nonconductive and residue free extinguishing agent that requires no cleanup.
These features and the versatility of design make the “FT’’ series fire extinguisher ideal for a
broad range of applications. The systems are ideal for small volumes, 150 cubic feet or less,
that are difficult to access. These applications would include marine, recreational vehicles,
commercial and industrial use where flammable liquids are likely source of fire.
Application Examples:
Engine Compartments (maximum 150 cubic feet)
Bow Thrusters
Small Generator Set Enclosures
Consoles
Electrical Enclosures
Flammable Liquid Storage Areas
Pump Enclosures
Alternative Fuel Storage Areas
Sea-Fire “FT” extinguishers are designed to induce a minimum atmospheric concentration of
10.0% within the protected compartment.* The specification table in this manual lists the
minimum and maximum approved compartment volume (size) allowable for each model.
Volume can be determined by multiplying the compartment’s length x width x height which
equals the volume in cubic feet or meters (LxWxH=V).
Exception: If the boat manufacturer has placed a permanently affixed label in the compart-
ment specifying the gross volume less the volume of permanently installed tankage, then
this volume may be used to determine the proper size extinguisher. Check specification table
for proper application before making installation.
*Reference: NFPA-2001 National Fire Protection Assoc. Boston, MA and UL 2166
Underwriters laboratories
SEA-FIRE “FT” SERIES AUTOMATIC FIRE SUPPRESSION SYSTEMS
FT — STINGER SPECIFICATION TABLE
AREA OF FM-200 @ DIAMETER X
MODEL PROTECTION 240 PSI HEIGHT TUBE PART # / LENGTH
CU.FT. CU.M.
AUTO AREA AREA LBS. KG INCH MM PART# FT. MM
FT-25 25 0.7 1.25 0.56 3.0 X 11.2 76 X 285 130-121 10 3000
FT-50 50 1.4 2.50 1.13 3.1 X 13.5 78 X 342 130-121 10 3000
FT-75 75 2.1 3.75 1.70 3.1 X 16.5 78 X 419 130-121 10 3000
FT-100 100 2.8 5.00 2.26 3.5 X 17.5 89 X 444 130-122 15 4500
FT-125 125 3.5 6.25 2.83 4.1 X 17.0 104 X 432 130-122 15 4500
FT-150 150 4.2 7.50 3.40 5.2 X 19.0 132 X 482 130-122 15 4500
CU. FT. = Cubic Feet FT. = Feet KG = Kilograms
CU.M. = Cubic Meters LBS. = Pounds MM = Millimeters
CAUTION: NEVER INSTALL A UNIT WITH A VOLUME RATING LESS THAN THE GROSS
VOLUME OF THE COMPARTMENT TO BE PROTECTED. DO NOT DEDUCT FOR
ENGINES, REMOVABLE TANKS OR OTHER EQUIPMENT.
2