Sanyo 85464359981002 Air Conditioner User Manual


 
72
8-4. Auto Address Setting
Basic wiring diagram: Example (1)
(S004)
1-1
1-2 1-3
1-8
• If link wiring is not used
(The inter-unit control wires are not connected to multiple refrigerant systems.)
Indoor unit addresses can be set without operating the compressors.
No. 1 unit settings
Unit
No. 1
Outdoor Unit
Indoor Unit
Remote controller
Inter-unit control wiring
Remote controller
cross-over wiring
(S004)
8
System address
(system 1 setting)
No. of indoor units
(8 units setting)
ON
1
2
ON
OFF
(S003) (S002)
1
(1) Automatic Address Setting from the Outdoor Unit
1. On the outdoor unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the
DIP switch (S003) is set to “0.” (These are the settings at the time of factory shipment.)
2. To set the number of indoor units that are connected to the outdoor unit to 8, on the outdoor unit control PCB set
the No. of indoor units rotary switch (S004) to “8.”
3. Turn ON the power to the indoor and outdoor units.
4. On the outdoor unit control PCB, short-circuit the automatic address pin (CN51) for 1 second or longer, then
release it.
(Communication for automatic address setting begins.)
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor unit control PCB turn OFF.)
5. Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 to 3, then use the remote controller and
complete automatic address setting.
Refer to “Automatic Address Setting from the Remote Controller.”
ON
ON
OFF
1
2
* To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.
The LED that indicates that automatic address setting is in progress turns OFF and the process is
stopped.
Fig. 8-5