Regency FG37-LPG Stove User Manual


 
10 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater
INSTALLATION
Diagram 2
HORIZONTAL INSTALLATIONS
Diagram 1
*Dia 2: Local codes or regulations may require
different clearances.
RESIDENTIAL AND MANUFACTURED HOMES/
MOBILE HOMES INSTALLATIONS
You will require the following components with your new Regency Rear Flued Room Sealed Freestanding Gas Stove. Please review your product
to make sure you have everything you need. In the event that you are missing any part, contact your dealer.
Note: These are the minimum pieces required.
Other parts may be required for your particular installation.
Minimum components for a Horizontal Installation:
946-110 Horizontal Termination Kit which includes:
1 946-201 6-5/8" dia. x 18" (168mm dia. x 457mm) Black Pipe
1 946-207 4" dia. x 18" (102mm dia. x 457mm) Aluminum Flue
1 946-584 Astro Riser Vent Terminal
1 946-202 Wall Penetration Heat Shield for Heat Sensitive walls
(Wall Thimble) (2 pcs)
1 640-545 Decorative Wall Trim (Black)
1 948-128 Tube Mill-Pac
Screws
Optional Components:
946-204 45
o
Elbow - 6-5/8" (168mm) Black pipe
and 4" (102mm) Aluminum Flue
946-205 Vinyl Siding Shield for Riser Vent
Terminal
946-208/P Flue Guard
940 Square Wall Thimble Cover*
942 Wall Penetration
Heat Shield*
* Simpson Dura-Vent components
1) Set the unit in its desired location. Check to
determine if wall studs are in the way when
the fluing system is attached. If this is the
case, you may want to adjust the location
of the unit.
2) Assemble the desired combination of pipe
and elbow to the appliance adapter with
pipe seams oriented down. Offset the pipe
seams as double seams in one place will
cause the outer pipe to take an oval shape.
Kit comes complete with 18" (457mm) of
straight flue - 6-5/8" (168mm) dia. black
outer pipe and 4" (102mm) dia. inner flue.
3) With the pipe attached to the stove, slide the
stove into its correct location, and mark the
wall for a 9-1/2" (241mm) (inside dimen-
sions) round hole. The center of the round
hole should line up with the centerline of the
horizontal pipe, as shown in diagram 1. Cut
and frame the 9-1/2 (241mm) round hole in
the exterior wall where the flue will be
terminated. If the wall being penetrated is
constructed of non-combustible material,
i.e. masonry block or concrete, a 7" (178mm)
diameter hole is acceptable.
Note:
a) The horizontal run of flue should have
a 1/4 inch (6mm) rise for every 1 foot
(305mm) of run towards the termina-
tion. Never allow the flue to run down-
ward. This could cause high tempera-
tures and may present the possibility of
a fire.
b) The location of the horizontal flue termi-
nation on an exterior wall must meet all
local and national building codes, and
must not be blocked or obstructed. For
External Flue Terminal Locations, see
diagram on page 7.
c) Snorkel Terminations:
For installations requiring a vertical rise
on the exterior of the building, Astro
Riser Vent Terminations as shown in
Dia. 2 is available. Follow the same
installation procedures as used for
standard Horizontal Termination.
NEVER install the Astro Riser vent up-
side down.