. Pump not properly primed.
2. Wrong direction of rotation.
3. Speed too low.
4. Total head too high.
".->,.-*9*,2=B*7-8;.*-
1. Air pockets or leaks in suction line.
2. Clogged impeller.
3. Foot valve strainer too small or clogged.
4. Excessive suction lift (over 15 feet).
5. Insufficient positive suction head (for hot water).
6. Total head more than that for which pump is
intended.
7. Excessively worn impeller and wearing rings.
"*92-'.*;8/8>95270
1. Misalignment or a bent shaft.
2. Sagging motor mounts (over-oiling).
>698<.< ;26.
1. Air leaks in suction line.
2. Excess air in water.
3. Water seal in stuffing box not functioning.
4
. Excessive suction lift and pump operating too near
shut-off point.
?.;58*-.-;2?270%72=
1. Head much lower than that for which pump is
designed.
2. Speed too high or higher than that contemplated.
.,1*72,*5$;8>+5.<*7-82<.
1. Misalignment.
2. Excessive suction lift or vapor binding (hot water).
3. Bent shaft and/or damaged bearings.
4. Suction and discharge piping not properly support-
ed and anchored.
#"&
$
"%"#
$>+.5.*7270
Establish a regular inspection schedule, the frequency
depending on the local water condition and severity of
service. Do not let the tubes clog up solidly. Clean out
deposits over 1/16" in thickness.
The heater may be cleaned from the side opposite the
water connections as shown, without breaking pipe
connections. It is preferable, however, to remove both
headers for better visibility through the tubes and to be
sure the residue does not get into the system. Note
that you do not remove the top pan or the heat
exchanger generally. After reaming with the auger,
mount the wire brush and clean out the debris remain-
ing in the tubes. Another method is to remove the heat
exchanger, ream tubes and immerse heat exchanger
in noninhibited de-scale solvent.
RAYPAK TUBE CLEANING KIT
Extension Pieces (5) Auger with Carbide Tip Wire Brush
P/N 052871F - 5/8 DIA.
P/N 052870F - 7/8 DIA.
Fig. 37: Raypak Tube Cleaning Procedure