Quadra-Fire MTVERNON-AE-PMH Stove User Manual


 
R
September 1, 2008
7034-106E
Page 15
Mt. Vernon Pellet Stove (AE)
We recommend a minimum of 60 inches
(1524mm) vertical, however above the eave
is preferred.
All three installations are approved for mobile
home installations. Must use 3 or 4 inch (76
to 102mm) “L” or “PL” Listed pellet venting or
Listed double wall pipe and Quadra-Fire Out-
side Air Kit in mobile homes. Single wall pipe
is approved for residential installations only.
*NOTE: Clearance to combustibles are for
standard pellet pipe. If pellet pipe manufac-
turer allows reduced clearances to their pipe,
reduced clearances are allowed.
C. Vertical into Existing Class A Chimney
D.
Through The Wall & Vertical - Exterior
Firestop
Flashing
Rain Cap
6 in.
(152mm)
Min.
Non-combustible Hearth Pad
3 in. (76mm) Min.
Clean-out Cover
12 in. (305mm) Minimum
Ceiling Support
3 to 6 in. (76-152mm)
Offset Adapter
6 in. (152mm) Class A
Chimney Connector
Adapter
3 to 3 in.
(76-76mm)
Top Vent Kit
Non-combustible Hearth Pad
Clean-out
Cover
Tee
Wall Thimble
Support
Bracket
every 60 in.
(1524mm)
12 in.
(305mm)
minimum
Rain
Cap
Flashing
2 in. (51mm) minimum
6 in. (152mm)
minimum
Figure 15.1
Figure 15.2
E. Vertical - Interior - Typical Installation
Firestop
Flashing
Rain Cap
6 in.
(152mm)
Min.
Non-combustible Hearth Pad
3 in. (76mm) Min.
Clean-out Cover
12 in.
(305mm)
Minimum
3 in. to 3 in.
(76-76mm)
Top Vent Kit
Figure 15.3