Page 38
7051-158B
December 6, 2011
R
EDGE 60 Pellet Fireplace
anges along the side.
8
Vent Information
A. Venting Termination Minimum Requirements
NOTICE:
Termination must exhaust above air inlet elevation.
• It is recommended that at least 60 inches (1.52m) of vertical
pipe be installed when appliance is vented directly through a
wall. This will create a natural draft, which will help prevent
the possibility of smoke or odor venting into the home during
a power outage.
• It will also keep exhaust from causing a nuisance or hazard
by exposing people or shrubs to high temperatures.
• The safest and preferred venting method is to extend the
vent vertically through the roof or above the roof.
J or K
X
V
M
I
H
A
V
G
B
V
V
A
B
V
F
V
C
B
B
E
L
V
D
V
Electrical
Service
V
N
V
N
V
N
N
V
Inside Corner
FIXED
CLOSED
OPEN
OPEN
FIXED
CLOSED
V
X
G
G
Termination Cap
Air Supply Inlet
Gas Meter
Restricted Area
O
P
Figure 37.1
A 12 in. Above Finish Grade (the grade surface
must be a non-combustible material
B 12 in. Open door or window: below or to the side
B 12 in. Open door or window: above
C 6 in. Permanently closed window: above, below
or to the side
D 18 in. Vertical clearance to a ventilated soffi t
located above the terminal within a hori-
zontal distance of 2 ft from the center-line
of the terminal
E 12 in. Clearance to unventilated soffi t
F 12 in. Clearance to outside corner
G 12 in. Clearance to inside corner
H 36 in. Above gas meter/regulator measured from
horizontal center-line of regulator
I 36 in. USA
72 in. Canada
Clearance to service regulator vent outlet
J 12 in. Clearance to non-mechanical air supply
inlet to the building or the combustion air
inlet to any other appliance
K 10 ft horizontal
3 ft vertical
Clearance to mechanical air supply
L 7 ft.
Above paved sidewalk, paved driveway
located on public property
M 12 in. Under an open veranda, porch, deck or
balcony
N See Note
below*
Electric service: above, below or to the
side (location must not obstruct or interfere
with access)
O 24 in. Adjacent building, fences and protruding
parts of the structure
P 12 in. Clearance above roof line for vertical
terminations
An Outside Air Kit is required on all installations. Outside Air Kit must be ordered separately.
24 in. Above grass, top of plants, wood or any other com-
bustible
12 in. Clearance from any forced air intake of other appli-
ance
12 in. Clearance horizontally from combustible wall
15 in. Vented directly through a wall, minimum length of
horizontal pipe
12 in. horizontal
12 in. vertical
Minimum horizontal or vertical terminations must
protrude from wall
*NOTE: Consult local building, fi re offi cials or authorities having
jurisdiction. Local codes or regulations may require different
clearances.
NOTICE:
Do NOT Terminate Vent:
• In any location that will allow fl ue gases or soot to enter
or stain the building.
• In any location which could create a nuisance or hazard.
• In any enclosed or semi-enclosed area such as a carport,
garage, attic, crawl space, under a sun deck or porch,
narrow walkway.
• Closely fenced area, or any location that can build up
a concentration of fumes such as a stairwell, covered
breezeway, etc.