Page 35
EDGE 60 Pellet Fireplace
C. Junction Box & Wiring Diagram
1. There is a 5 screw terminal connection bar that is located
in the lower left side of the fi replace above the slide rails.
Figure 34.3.
2. Route the 25 foot (7.62m) long white wall control wire that
is supplied in the component pack through the rubber
grommet in the left side of the fi replace outer can. Figure
34.1
3. The center 3 screws are for the thermostat wall control
wires and the 2 outer screws are mounting screws and
should not have wires attached to them.
The thermostat wires are color coded. The green wire
is on the top, the white in the middle and the red on the
bottom.
5. Attach the wall control wire to the thermostat wall control
Follow the directions on page 35. Do not pinch the con-
trol wires with any staples between the fi replace and wall
control. Figure 35.1 on page 35.
6. Bend back the 3 red spade connectors towards inside of
outer can and away from the fi replace. Wires should not
be in the way when the fi replace is rolled out on the rail
system.
D. Connecting Wall Control To Fireplace
Caution! The fi replace should be securely attached to the
fl oor prior to making fi nal electrical connections.
WARNING
Shock Hazard
• A grounded metal outlet power supply box is
required for all installations.
• Provides a positive ground path to earth for
outer can of the fi replace.
• Protects against possible electrical shock.
1. Disconnect power supply providing power to the outlet
box you intend to use.
2. The power supply cord is inside a 7-1/2 foot (2.29m)
long 3/8 inch (9.5mm) fl exible conduit cable located and
attached to the left side of the outer can. Figure 34.1.
The cable comes with an insulated snap-in connection.
3. Locate the metal outlet box within 7-1/2 feet (2.29m) of
the fi replace. (Note: Metal outlet box not supplied).
4.
Feed the power cord into the 1/2 inch (12.7mm) standard
knockout of the outlet box and then press the connection
into the metal outlet box.
5. The power supply cord has black, white and green wires
to connect to the outlet box.
Black wire: Connects to 120V AC 15-20 amp circuit
White wire: Connects to neutral wire
Green wire: Connects to ground wire and outlet box
6. Ensure the 2 green grounding wires are securely attached
to the grounding screw. Figure 34.2.
Power Supply Cord inside 7.5 ft
(2.29m) Flexible Cable
Thermostat Wall Control Wire
Both Green Grounding Wires
Attach to Grounding Screw
Grounding
Screw
Black
Wires
White
Wires
Figure 34.1 - Power Supply Cord
and Wall Control Wire
Figure 34.2 - Metal Outlet Box
Green
White
Red
Matching
Color Dots
Fireplace Left Lower Front
Figure 34.3 - Terminal Connec-
tion Bar