4.3 SUMMARY OF LED COMBINATIONS AND THEIR MEANING
Use the table below to determine the condition of the panel.
LEDs LIT LED CONDITION PANEL STATUS
POWER CONSTANT GREEN The panel is supplied with power, and has no faults / fires (System Normal)
GEN FLT
ONLY
CONSTANT YELLOW Problem with keyswitch connections
GEN FLT &
SUPPLY FLT
CONSTANT YELLOW
FLASHING YELLOW
There is a problem with either the mains supply or the battery backup
GEN FLT &
EARTH FLT
CONSTANT YELLOW
FLASHING YELLOW
There is a wiring problem. One of the cables is touching the earth screen.
GEN FLT &
ZONAL FLT
CONSTANT YELLOW
FLASHING YELLOW
There is an open circuit fault in the wiring of the zone indicated.
GEN FLT &
ZONAL FLT
GEN S/C
CONSTANT YELLOW
FLASHING YELLOW
FLASHING YELLOW
There is a short circuit fault in the wiring of the zone indicated.
GEN FLT &
SND FLT
CONSTANT YELLOW
FLASHING YELLOW
There is an open circuit fault in the wiring of one or both of the sounder
circuits
GEN FLT &
SND FLT
GEN S/C
CONSTANT YELLOW
FLASHING YELLOW
FLASHING YELLOW
There is a short circuit fault in the wiring of one or both of the sounder
circuits
GEN FLT &
SYSTEM FLT
CONSTANT YELLOW
CONSTANT YELLOW
A processor fault has occurred. To reset, turn keyswitch on then back off. If
problem persists, consult your dealer.
GEN FIRE
ONLY
CONSTANT RED A manual evacuation has occurred.
The sounders will be active.
GEN FIRE &
ZONE FIRE
CONSTANT RED
CONSTANT RED
A fire has occurred in the zone indicated.
The sounders will be active.
GEN FIRE &
ZONE FIRE &
GEN DISABLE
& DEL
CONSTANT RED
CONSTANT RED
CONSTANT YELLOW
CONSTANT YELLOW
A fire has occurred in the zone indicated.
The sounders have a delay set, and will become active after the
programmed delay. To override the display, press delay override.
GEN DISABLE
FLASHING YELLOW
(FAST – 4 HZ)
The panel is ready for selecting disable or test mode
GEN DISABLE
FLASHING YELLOW
(SLOW – 0.5 HZ)
The panel is in SELECT DISABLEMENT MODE
GEN DISABLE
ZONE DISABLE
FLASHING YELLOW
(SLOW – 0.5 HZ)
The user is scrolling through zones to select which one to disable/or user
has just enabled the zone.
GEN DISABLE
ZONE DISABLE
CONSTANT YELLOW
CONSTANT YELLOW
The indicated zone is disabled.
GEN DISABLE
DEL
CONSTANT YELLOW
CONSTANT YELLOW
The Sounders are delayed by the amount set on the rotary switch.
GEN TEST
ZONE DISABLE
FLASHING YELLOW
FLASHING YELLOW
(VERY SLOW – 0.25 HZ)
The indicated zone is in Test Mode.
4.4 CHECKING THE PANELS INDICATION LEDS
Turn the key switch to “Controls Enabled” position then press the LED test button (Button 4). All the LEDs on the
front panel will light, and the panel’s internal buzzer will also sound.