Premier Fire Alarm Control Panel Smoke Alarm User Manual


 
PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-102
PAGE 10
Issue: 1.3 Authorised: GH Date: 9/6/2004
7. DISABLEMENTS
7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM.
Certain parts of this Fire Alarm Panel can be temporarily disabled (i.e. switched off) to suit prevailing conditions. For
example, if there is a risk of a False Alarm in a zone, for example, from vehicle exhaust smoke in a loading bay, it is
possible for the user to disable that zone during the risk period and then enable it again afterwards. During a disablement
of a zone(s), no fire or fault signal will be processed for that zone(s). Only zone(s) in a non-alarm state can be disabled,
that is zones already in fire cannot be disabled.
External sounders can also be disabled as could be required in certain conditions.
7.2 TO DISABLE A ZONE AND/OR EXTERNAL SOUNDERS.
1. Turn control key to “Controls Enable” position;
2. Press “Engineer” switch momentarily, this will cause General Disablement LED to flash (fast). This means the
panel is in disable/enable mode;
3. Press scroll (No. 4) switch once and this will cause the General Disablement LED to flash (slow);
4. Press scroll (No. 4) switch once again and this will cause Zone 1 Disablement LED to light steady;
5. Pressing scroll (No. 4) switch will cause the zone disablement LED to toggle to zone 2 and so on;
POWER
GEN-FIRE
GEN-FAULT
SUPPLY FLT
SYSTEM FLT
GEN-S/C
DEL
GEN-ZONE TEST
GEN-DISABLEMENT
1
8
765432
18765432
FIRE / ZONES
ZONAL FAULT / DISABLEMENT / TEST
12
3
4
ENGINEER
STOP-START SILENCE RESET SCROLL /
/ LED TEST
FLT TONE
DELAY
OVERRIDE
FLT
6. Select zone to be disabled. For example, if Zone 3 is selected and with Zone 3 disablement LED lit (steady) and
General Disablement LED flashing slow, pressing “Engineer” will cause General Disablement LED light to change
to steady. This means that zone 3 is now disabled;
7. Switch controls key to off position, then both the disabled Zone Disablement LED and the General Disablement
LED will remain lit (steady.
7.3 TO ENABLE A ZONE AND/OR EXTERNAL SOUNDERS.
1. Turn key to “Controls enable” position (since a zone is already disabled at this time, the General Disablement LED
with stay lit (steady);
2. Press “Engineer” switch once and this will cause the General Disablement LED to flash (fast);
3. Press scroll (No. 4) switch until the light is steady at the disabled zone;
4. Press “Engineer” and this will cause the General Disablement LED to flash (slow);
5. Turn control Key to “Off” position and this will turn off the General Disablement and Zone Disablement LEDs.
NOTES:
The option of disabling or enabling zones 2, 3, 4, 5, 6, 7 and 8 is only available if these zones are present on the
panel