Potterton Solar - Solar Thermal Domestic Hot Water System 21
Commissioning record
T
he following chart should be completed during Commissioning of the system.
Installer: _______________________________
Contact details: _______________________________
Original installation date: _______________________________
General Commissioning
All pipework correctly installed, identified and
e
arth bonded
Solar primary system filled with heat transfer
fluid supplied
System pressure test carried out
S
olar expansion vessel charge pressure checked
and set bar
Air vented from system
Exposed pipework insulated using high-temp and
weather resistant insulation
Panel fixing bracket positions weatherproofed
where necessary
Panel fixings checked and secure
Hydraulic Station
System pressure when cold bar
Solar primary flow when cold l/min
Isolating/non-return valves (flow and return) in
operating position
Solar Collector Panels
Panels visually inspected for defects
Collector temperature sensor correctly installed
and secured
Pipe entry points to building weatherproof
Solar DifferentialTemperature Controller
Record all operational parameters set
(see separate table)
Pump operation tested in automatic and manual
modes
All cables correctly installed and secured
Suitably fused isolating device installed
Solar Cylinder
Cylinder installed and commissioned in
accordance with cylinder installation instructions
Adjustable in menu Typical Current
"Programming" adjustment adjustment
Storage tank1: 65°C
Maximum storage temperature
Storage tank1: 7 K
switch-on difference (dTon)
Storage tank1: 3 K
switch-off difference (dToff)
Storage tank2: 90°C
Maximum storage temperature
Storage tank2: 7 K
switch-on difference (dTon)
Storage tank2: 3 K
switch-off difference (dToff)
Minimum pump power on 100%
rotational speed regulation
Switch-on temperature of 40°C
thermostat function
Hysteresis of thermostat function 10 K
2nd temperature differential 65°C
controller maximum temperature Tmax
2nd temperature differential controller 7 K
hysteresis dTmax
Adjustable in menu Typical Current
"Basic adjustments" adjustment adjustment
Switching on or off the function 0 = off
collector protection
Temperature at which the collector 120°C
protection function is active
Switching on or off the function 0 = off
recooling (only when the collector
protection is on)
Temperature to which the storage 40°C
tank is recooled when collector
protection function is on
Function for time-controlled 0 = off
circulation in operation with
tube collectors
Switching on or off the function 0 = off
energy productivity measurement
Choice of glycol types used 0 = Anro
Mixture ratio of coolants 50%
Litres per impulse of the flowmeter 1.0 L/I
Switching on or off the function 0 = off
antifreezing
Temperature at which the antifreezing -1°C
is active
Alternative choice of the cooling, 0 = none
thermostat function or the 2nd
temperature differential controller
System type type 0
Time control in secs 240
Storage priority 1
Solar differential temperature controller - operational parameters
If any factory values are changed please enter the new values in the
table below.