Page 16 of 40
Power On, PEA2 is reset to the present input. To manually
reset the value
PEA2PEA2
PEA2PEA2
PEA2 must be in the lower display. Press
the ENTER key to reset.
PEA2PEA2
PEA2PEA2
PEA2 will be reset and display the
present input value.
UAL2UAL2
UAL2UAL2
UAL2 The Valley feature stores the lowest input the Instrument
has measured for Zone 2 since the last reset or Power On.
At Power On,
UAL2UAL2
UAL2UAL2
UAL2 is reset to the present input. To manually
reset the value
UAL2UAL2
UAL2UAL2
UAL2 must be in the lower display. Press
the ENTER key.
UAL2UAL2
UAL2UAL2
UAL2 will be reset and display the present
input value.
LOrELOrE
LOrELOrE
LOrE
(Option C4, Serial Communications) Local / Remote Sta-
tus: Select
LOCLOC
LOCLOC
LOC
or
rErE
rErE
rE
.
LOCLOC
LOCLOC
LOC
The host computer is advised not to send remote
commands. Any write commands sent to the
controls will be rejected.
rErE
rErE
rE
The host computer is allowed to send write
commands.If the control is not addressed within
the time set in the
nAtnAt
nAtnAt
nAt
(No Activity Timer, see
Secure Menu) the
CHEC LorECHEC LorE
CHEC LorECHEC LorE
CHEC LorE
error message will be
displayed.
AddrAddr
AddrAddr
Addr
(Option C4, Serial Communications) Control Address: Set
from
1
to
3FF
. This number (hexadecimal, base 16) must
match the address number used by the host computer.
Viewed only in this menu. The value displayed is for Zone
1. The address for Zone 2 is the value for Zone 1 plus one.
To change this parameter, see
AddrAddr
AddrAddr
Addr
in the Secure Menu.
End of Secondary Menu when
EditEdit
EditEdit
Edit is set to
00
00
0.